HGM6100U Series Automatic Control Module
HGM6100U Automatic Genset Controller ISSUE 2014-10-28 Version 1.2 Page 26 of 39
7.2 PROGRAMMABLE OUTPUT 1-4 TABLE (TABLE 2)
No.
Items
Description
0
Not Used
Output is disabled when this item is selected.
1
Common Alarm
Including all shutdown alarm and warning alarm.
When a warning alarm occurs, the alarm won
’
t
self-lock; When a shutdown alarm occurs, the
alarm will self-lock until alarm is reset.
2
ETS Control
Used for the genset with stop solenoid. Pick-up
when idle speed is over while disconnect when
ETS delay is over.
3
Idle Control
Used for the genset with idle speed. Pick-up when
crank while disconnect when enter into warming
up. Pick-up when stop idle while disconnect when
genset stop completely.
4
Preheat Control
Close before started and disconnect before
powered on.
5
Gens Close
When close time is set as 0, it is continuous
closing.
6
Mains Close
HGM6110UC
without.
7
Open Breaker
When close time is set as 0, Open Breaker is
disabled.
8
Accelerate Control
Pick-up when enter into warming up time.
Disconnect when raise speed auxiliary input
active.
9
Decelerate Control
Pick-up when enter into stop idle or ETS solenoid
stop (shutdown alarm). Disconnect when droop
speed auxiliary input active.
10
Genset Run Output
Output when genset is in normal running,
disconnect when rotating speed is lower than
engine speed after fired.
11
Fuel Pump Control
Pick-up when the fuel level lower than the open
threshold or low fuel level warning is active;
disconnect when the fuel level over the close
threshold and the low fuel level warning input is
disabled.
12
High Speed Control
Output when it enter into warming up time, and
disconnect after cooling.
13
System In Auto Mode
The controller is in Auto Mode.
14
Reserved
15
Reserved
16
Reserved
17
Reserved