HGM6100U Series Automatic Control Module
HGM6100U Automatic Genset Controller ISSUE 2014-10-28 Version 1.2 Page 30 of 39
8 PARAMETER SETTING
After controller powered on, press
to enter into the parameters setting menu:
1) Parameters Setting
2) Information
3) Language
1) Parameters Setting
"1234" can set the part of the items in Table 1 during inputting password,; "0318"
can set all items in Table 1.
If more parameter items need to be set, such as voltage and current calibration,
please contact with the factory.
NOTE:
1)
HGM6110UC
, there are not items 1-5 in table1; programmable output 1-4 have no
digital outputs about mains.
2) Please modify the parameters in standby mode (crank conditions, auxiliary input
and output configuration, multi delays, etc.) otherwise shutdown alarm or other
abnormal conditions may appear.
3) The over-voltage threshold must be greater than the under-voltage threshold;
otherwise over-voltage and under-voltage will occur at the same time.
4) The over-speed threshold must be greater than under-speed threshold, otherwise
over speed and under speed will occur at the same time.
5) Set frequency value (after crank disconnect) as low as possible, in order to
disconnect starter quickly.
6) Programmable input 1-5 cannot be set as the same items, otherwise it cannot
realize correct function; programmable output 1-4 can be set as the same item.
7) If need to shut down after cooling, please set any input as " stop after cooling ",
then connect this input to ground.
2) Information
LCD will display some information of controller, such as software version, issue date.
Note:
Pressing
will display the status of digital inputs and outputs.