HGM6100U Series Automatic Control Module
HGM6100U Automatic Genset Controller ISSUE 2014-10-28 Version 1.2 Page 12 of 39
4.4 MANUAL START/STOP OPERATION
1)
HGM6120UC,
Auto Mode is active when press
and its indicator illuminates.
Press
, then controller enters into
“
Manual Test Mode
”
and its indicator is
illuminating. Under both of the modes, press
to start genset, it can automatically
detect crank disconnect and accelerate to high speed running. If there is high
temperature, low oil pressure, over speed and abnormal voltage during genset
running, controller can protect genset to stop (detail procedures please refer to
No.4~9 of Auto start operation). Under Manual Mode, switch won
’
t transfer
automatically, it is necessary to press
to transfer load. Under
“
Manual Test Mode
”
,
after genset runs well in high speed, no matter mains is normal or not, loading switch
will be transferred to gens.
2)
HGM6110UC
, Auto Mode is active when pressing
, and its indicator is
illuminating. Then press
to start genset, it can automatically detect crank
disconnect and accelerate to high speed running. If there is high temperature, low oil
pressure, over speed and abnormal voltage during running, controller can protect
genset to stop quickly (detail procedures please refer to No.4~9 of Auto start
operation). After genset runs well in high speed, press
and gens take load.
3) Manual stop, pressing
can shut down the running genset (detail procedures
please refer to No.3~7 of Auto stop operation).