HEM4300 Engine Controller User Manual Page 28 of 55
No.
Item
Range
Default
Description
2
Open Action
(0-2)
0
0: Warning; 1: Shutdown; 2: No Action.
3
Display Unit
(0-1)
0
0: °C; 1: °F
4
Over
Temp
Shutdown
Enable
(0-1)
0
When temp. sensor value is larger than
this value, controller issues temp. high
shutdown alarm; This value is detected
only after safety on delay.
Set
((-50)-300)°C
98
Delay
(0-3600)s
3
5
Over
Temp
Warn
Enable
(0-1)
1
When temp. sensor value is over this
value, controller issues temp. high
shutdown alarm; This value is detected
only after safety on delay.
Set
((-50)-300)°C
95
Return
((-50)-300)°C
93
Delay
(0-3600)s
5
6
Under Temp
Warn
Enable
(0-1)
0
When temp. sensor value is less than
this value, controller issues temp. low
warning alarm; This value is detected
always.
Set
((-50)-300)°C
10
Return
((-50)-300)°C
25
Delay
(0-3600)s
5
7
Heater
Control
Enable
(0-1)
0
When temp. sensor value is less than
this value, heater control outputs.
On
((-50)-300)°C
50
Off
((-50)-300)°C
55
Max.
On
Time
(0-3600)min
60
8
Cooler
Control
Enable
(0-1)
0
When temp. sensor value is larger than
this value, cooler control outputs.
On
((-50)-300)°C
95
Off
((-50)-300)°C
92
Max.
On
Time
(0-3600)min
60
9
Preheat
Output
Correlation
Enable
(0-1)
0
After it is enabled, if engine
temperature is larger than set value,
preheat stops output, preheat delay is
over.
Set Value
(0-300)°C
5
10
Custom Curve
Corresponding curve needs to be set in
choosing
custom
resist./voltage/current type curve.
Engine Oil Pressure Setting
1
Curve Type
(0-15)
9
SGD. See table 13.
2
Open Action
(0-2)
0
0: Warning; 1: Shutdown; 2: No Action.
3
Display Unit
(0-2)
0
0: kPa 1: bar 2: psi
4
OP
Low
Shutdown
Enable
(0-1)
0
When oil pressure sensor value is less
than this value, controller issues OP
low shutdown alarm. This value is
detected only after safety on delay.
Set
(0-1000)kPa
103
Delay
(0-3600)s
3
5
OP Low Warn
Enable
(0-1)
0
When oil pressure sensor value is less
than this value, controller issues OP
low warning alarm. This value is
detected only after safety on delay.
Set
(0-1000)kPa
124
Return
(0-1000)kPa
138
Delay
(0-3600)s
5
6
Custom Curve
Corresponding curve needs to be set in