HEM4300 Engine Controller User Manual Page 32 of 55
No.
Item
Range
Default
Description
level.
Aux. Input 2
1
Contents Setting
(0-59)
3
Alarm reset. Details see Table 12.
2
Active Type
(0-1)
0
0: Close 1: Open
3
Active Electric Level
(0-1)
0
0: Low electric level; 1: High electric
level.
Aux. Input 3
1
Contents Setting
(0-59)
26
High temp shutdown Input. Details see
Table 12.
2
Active Type
(0-1)
0
0: Close 1: Open
3
Active Electric Level
(0-1)
0
0: Low electric level; 1: High electric
level.
Aux. Input 4
1
Contents Setting
(0-59)
27
Low oil pressure Shutdown Input.
Details see Table 12.
2
Active Type
(0-1)
0
0: Close 1: Open
3
Active Electric Level
(0-1)
0
0: Low electric level; 1: High electric
level.
Aux. Input 5
1
Contents Setting
(0-59)
29
Raise speed input. Details see Table
12.
2
Active Type
(0-1)
0
0: Close 1: Open
3
Active Electric Level
(0-1)
0
0: Low electric level; 1: High electric
level.
Aux. Input 6
1
Contents Setting
(0-59)
30
Drop speed input. Details see Table 12.
2
Active Type
(0-1)
0
0: Close 1: Open
3
Active Electric Level
(0-1)
0
0: Low electric level; 1: High electric
level.
Aux. Input 7
1
Contents Setting
(0-59)
1
Users defined. Details see Table 12.
2
Active Type
(0-1)
0
0: Close 1: Open
3
Active Electric Level
(0-1)
0
0: Low electric level; 1: High electric
level.
4
Active Range
(0-3)
0
0: After safety on delay; 1: From Start;
2: Always; 3: Inactive.
5
Active Action
(0-2)
0
0: Warning; 1: Shutdown; 2: Indication.
6
Active Delay
(0-600.0)s
2.0
Time from detecting input is active to
confirm.
7
Input Description
User defined.
Aux. Input 8
1
Contents Setting
(0-59)
0
Not used. Details see Table 12.
2
Active Type
(0-1)
0
0: Close 1: Open
3
Active Electric Level
(0-1)
0
0: Low electric level; 1: High electric