HEM4300 Engine Controller User Manual Page 34 of 55
No.
Item
Range
Default
Description
Alternate Configuration 2
1
Enable Choose
(0-1)
0
0: Disable 1: Enable
2
Engine Rated Speed
(0-6000)r/min 2000
When this is enabled, if input is
configured to “Alt Config. 2 Active” and
input is active, speed shall be adjusted
according to alternate configuration
settings.
3
Engine Idle Speed
(0-100.0)%
40.0
4
Speed Control Upper Limit
(0-6000)r/min 2000
5
Load Output
(0-3)
2
0: Load Control;
1: Load Control 1;
2: Load Control 2;
3: Load Control 3.
6
Load Rate High Speed
(0-100.0)%
70.0
When controller issues load rate high
warning signal, it will drop speed to the
value of high load rate.
Alternate Configuration 3
1
Enable Choose
(0-1)
0
0: Disable 1: Enable
2
Engine Rated Speed
(0-6000)r/min 2000
When this is enabled, if input is
configured to “Alt Config. 3 Active” and
input is active, speed shall be adjusted
according to alternate configuration
settings.
3
Engine Idle Speed
(0-100.0)%
40.0
4
Speed Control Upper Limit
(0-6000)r/min 2000
5
Load Output
(0-3)
3
0: Load Control;
1: Load Control 1;
2: Load Control 2;
3: Load Control 3.
6
Load Rate High Speed
(0-100.0)%
70.0
When controller issues load rate high
warning signal, it will drop speed to the
value of high load rate.
Maintenance Setting
1
Password Set
(0-65534)
01234
It used for entering maintenance
parameter setting.
Caution!
Default password is “01234”; It
can be changed by operator for purpose of
preventing
others
changing
controller
advanced configuration randomly. Please
remember clearly after change. If it is
forgotten, please contact company service
personnel.
2
Maintenance 1 Set
(0-1)
0
0: Disable 1: Enable
Maintenance time, maintenance time
due
action,
maintenance timing
method, reset maintenance time can
be set at the same time; After
maintenance, maintenance time due
3
Maintenance 2 Set
(0-1)
0
4
Maintenance 3 Set
(0-1)
0
5
Maintenance 4 Set
(0-1)
0
6
Maintenance 5 Set
(0-1)
0
7
Maintenance 6 Set
(0-1)
0