HEM4300 Engine Controller User Manual Page 26 of 55
No.
Item
Range
Default
Description
Hold” is set 0; When it is not 0, it is time
after ETS delay before complete stop.
12
After Stop Time
(0-3600)s
0
Time from complete stop to standby
status.
Engine Setting
1
Engine Type
(0-39)
39
Default: 39: GTSC1-PLUS.
2
ECU Alarm Shut
(0-1)
0
0: Disable 1: Enable
NOTE:
When engine detects red light alarm, it
will stop when it is enabled.
3
ECU Source Address
(0-255)
3
Source address of ECU speed control
communication.
4
Rated Speed
(0-6000)r/min 2000
Provide standard for over speed, under
speed and load speed detection.
5
Idle Speed Set
(0-100.0)%
40.0
Set value is percentage of rated speed.
Please stabilize speed to set value
when idle running is required.
6
Start Attempts
(1-10)times
1
Maximum start times in case of failed
start; when this number is reached,
controller shall issue Failed to Start
signal.
7
Crank Disconnect
(0-2)
2
Please refer to Table 14.
There are two kinds of disconnect
conditions for engine and starter. They
can be used separately or together,
aiming to separate starter motor and
engine as soon as possible.
8
Disconnect Speed
(0-200)%
24.0
Set value is the percentage of rated
speed; when speed is above the set
value, starter shall disconnect; Please
refer to the rear installation.
9
Disconnect OP
(0-1000)kPa
200
When Oil Pressure is above pre-set
value, starter shall disconnect. Please
refer to the following installation
instruction.
10
Overspeed
Warn
Enable
(0-1)
1
Set value is the percentage of rated
speed; When controller detects engine
speed is above the set threshold, it
issues warning signal.
Set
(0-200.0)%
110.0
Return
(0-200.0)%
108.0
Delay
(0-3600)s
5
11
Overspeed
Shutdown
Enable
(0-1)
0
Set value is the percentage of rated
speed; When controller detects engine
speed is above the set threshold, it
issues shutdown alarm signal.
Set
(0-200.0)%
114.0
Delay
(0-3600)s
2
12
Speed Signal
Loss
Action
(0-2)
0
0: Warning; 1: Shutdown; 2: No Action.
Delay
(0-3600)s
5
Time from detecting speed is 0 to