HEM4300 Engine Controller User Manual Page 33 of 55
No.
Item
Range
Default
Description
level.
Aux. Outputs
Aux. Output 1
1
Contents Setting
(0-139)
29
Fuel relay output. Details see Table 11.
2
Output Type
(0-1)
0
0: Normally open; 1: Normally close
Aux. Output 2
1
Contents Setting
(0-139)
28
Starting relay output;
Please refer to Table 10 for details.
2
Output Type
(0-1)
0
0: Normally open; 1: Normally close
Aux. Output 3
1
Contents Setting
(0-139)
30
Idle speed control. Details see Table
11.
2
Output Type
(0-1)
0
0: Normally open; 1: Normally close
Aux. Output 4
1
Contents Setting
(0-139)
26
Load control. Details see Table 11.
2
Output Type
(0-1)
0
0: Normally open; 1: Normally close
Aux. Output 5
1
Contents Setting
(0-139)
39
Normal running output. Details see
Table 11.
2
Output Type
(0-1)
0
0: Normally open; 1: Normally close
Aux. Output 6
1
Contents Setting
(0-139)
42
Common alarm. Details see Table 11.
2
Output Type
(0-1)
0
0: Normally open; 1: Normally close
Aux. Output 7
1
Contents Setting
(0-139)
0
Not used. Details see Table 11.
2
Output Type
(0-1)
0
0: Normally open; 1: Normally close
Aux. Output 8
1
Contents Setting
(0-139)
0
Not used. Details see Table 11.
2
Output Type
(0-1)
0
0: Normally open; 1: Normally close
Alternate Configuration Setting
Alternate Configuration 1
1
Enable Choose
(0-1)
0
0: Disable 1: Enable
2
Engine Rated Speed
(0-6000)r/min 2000
When this is enabled, if input is
configured to “Alt Config. 1 Active” and
input is active, speed shall be adjusted
according to alternate configuration
settings.
3
Engine Idle Speed
(0-100.0)%
40.0
4
Speed Control Upper Limit
(0-6000)r/min 2000
5
Load Output
(0-3)
1
0: Load Control;
1: Load Control 1;
2: Load Control 2;
3: Load Control 3.
6
Load Rate High Speed
(0-100.0)%
70.0
When controller issues load rate high
warning signal, it will drop speed to the
value of high load rate.