ALC404 LIGHTING TOWER CONTROLLER USER MANUAL
ALC404 Lighting Tower Controller 2018-11-06 Version 1.1 Page 50 of 83
Category
Parameters
Range
Default
Description
Delay
pressed before the delay
expired is one condition for
judging whether controller
enters into deep sleep
mode.
NOTE: The remaining parameters can only be configured by the PC software.
7.3
FLEXIBLE SENSOR 1 SETTINGS
Table 20
– Flexible Sensor 1 Parameter Settings
No.
Parameter
Range
Default
Description
1
Sensor Type
(0~3)
1
0 Not Used
1 Temp. Sensor
2 Pressure Sensor
3 Fuel Level Sensor
2
Curve Type
(0~15)
11
Details of sensor curve
please to see
7.6 SENSOR
CURVE SELECTION.
3
Open Circuit Action
(0~2)
0
0 Warning
1 Shutdown
2 No Action
4
Display Unit
(0~1)
0
0:
℃
1:
℉
5
Sensor High
Shutdown
(0~1)
(0~1)
1
0 Disabled 1 Enabled
6
Set Value
(0~1000)
℃
98
7
Delay
(0~3600)s
3
8
Sensor Low
Shutdown
Enable
(0~1)
0
0 Disabled 1 Enabled
9
Set Value
(0~1000)
℃
0
10
Delay
(0~3600)s
3
11
Sensor High
Warning
Enable
(0~1)
1
0 Disabled 1 Enabled
12
Set Value
(0~1000)
℃
95
13
Return Value
(0~1000)
℃
93
14
Delay
(0~3600)s
5
15
Sensor Low
Warning
Enable
(0~1)
0
0 Disabled 1 Enabled
16
Set Value
(0~1000)
℃
70
17
Return Value
(0~1000)
℃
75
18
Delay
(0~3600)s
5s
19
User-defined
Sensor Curve
1
st
point X
(Resistance)
(0~1000)
0
Sensor curves can be user
defined. X-axis and Y-axis
separately contains 8 points.
Unit of X-
axis is Ω;
Units of Y-axis are as
20
2
nd
point X
(Resistance)
(0~1000)
21
21
3
rd
point X
(Resistance)
(0~1000)
28