ALC404 LIGHTING TOWER CONTROLLER USER MANUAL
ALC404 Lighting Tower Controller 2018-11-06 Version 1.1 Page 28 of 83
No.
Type
Description
12
Over Current
If it is enabled, when controller detects the current is higher than the
maximum limit of preset value, meanwhile, action select as shutdown, it
will send a shutdown signal and the corresponding alarm information will
be displayed on the LCD.
13
Fail To Start
If gen-set start failure within setting of start times, it will send a shutdown
signal and the corresponding alarm information will be displayed on the
LCD.
14
Pressure Sensor
Open Circuit
When controller detects the Pressure Sensor Open Circuit input is active,
it will send shutdown signal and the corresponding alarm information will
be displayed on the LCD.
15
Input 1 Shutdown
When input port 1 is selected as user defined and action type choose
shutdown alarm, if input port is active, controller will send warning signal
and the corresponding alarm information will be displayed on the LCD. If
input name
is configured by users as xxx, then ―xxx Shutdown‖ will be
displayed on the LCD.
16
Input 2 Shutdown
When input port 2 is selected as user defined and action type choose
shutdown alarm, if input port is active, controller will send warning signal
and the corresponding alarm information will be displayed on the LCD. If
input name i
s configured by users as xxx, then ―xxx Shutdown‖ will be
displayed on the LCD.
17
Input 3 Shutdown
When input port 3 is selected as user defined and action type choose
shutdown alarm, if input port is active, controller will send warning signal
and the corresponding alarm information will be displayed on the LCD. If
input name
is configured by users as xxx, then ―xxx Shutdown‖ will be
displayed on the LCD.
18
Input 4 Shutdown
When input port 4 is selected as user defined and action type choose
shutdown alarm, if input port is active, controller will send warning signal
and the corresponding alarm information will be displayed on the LCD. If
input name
is configured by users as xxx, then ―xxx Shutdown‖ will be
displayed on the LCD.
19
Input 5 Shutdown
When input port 5 is selected as user defined and action type choose
shutdown alarm, if input port is active, controller will send warning signal
and the corresponding alarm information will be displayed on the LCD. If
input name is configured by users as xxx, then
―xxx Shutdown‖ will be
displayed on the LCD.
20
Low Fuel Level
When controller detects the Low Fuel Level input is active, it will send
shutdown signal and the corresponding alarm information will be
displayed on the LCD.
21
Sensor 1 Low
If it is enabled, when controller detects the sensor 1 value is lower than
the minimum limit of preset value, it will send shutdown signal and the
corresponding alarm information will be displayed on the LCD. If the
sensor name is configured by users as xxx, then ―xxx Low‖ shutdown
information will be displayed on the LCD.