ALC404 LIGHTING TOWER CONTROLLER USER MANUAL
ALC404 Lighting Tower Controller 2018-11-06 Version 1.1 Page 39 of 83
Category
Parameters
Range
Default
Description
percentage of starting
battery rated voltage
Delay
(0~3600)s
20
Battery Over
Voltage Warning
Enable
(0~1)
1
0 Disabled 1 Enabled
Set Value
(0~200)%
125
The setting value is
percentage of starting
battery rated voltage
Return
(0~200)%
120
The return value is
percentage of starting
battery rated voltage
Delay
(0~3600)s
20
Under Starting
Battery Voltage
Start Set
Work Mode
Select
(0~3)
0
0 Invalid
1 Auto Mode Active
2 Manual Mode Active
3 Auto and Manual Mode
Active
Max. Run
Time
(0.1~100.0)h
4.0
If battery under voltage
starts up, when charging
time exceeds the setting
limit, engine will
automatically shut down,
and then charging will stop.
Full Charge
Delay
(0~1000)min
60
It is the time from battery
voltage exceeds full
charged voltage limit to
under voltage start end.
Start Value
(0~200)%
80
The setting value is
percentage of starting
battery rated voltage. When
controller detects that
genset in standby status
and battery voltage bellows
under voltage start limit, it
will execute auto under
voltage start logic.
Full Charge
Value
(0~200)%
125
The setting value is
percentage of starting
battery rated voltage. When
controller detects that
genset in under voltage
start maintenance status
and genset is normal
running, if battery voltage