ACC4100 Diesel Air Compressor Controller User Manual Page 38 of 52
9
PARAMETERS SETTING
Press
key and enter into setting menu after controller is power on. The menu list is as below:
>Return
>Parameters Set
>Override Mode
>DPF Regeneration
>Language
>LCD Backlight
>Event Log
>Module Info
Select “Parameters Set” and input correct password (default: 1234) to enter setting interface.
Parameter setting process is as below:
Parameters Set
Screen 1: Enter setting, press
to change settings, press
to
enter setting (Screen 2), press
to return. Or select “Return” by
pressing
and
and press
to go back to previous screen.
>Return
>Module Set
>Timers Set
>Engine Set
Timers Set
Screen 2: Press
to change settings, press
to enter setting
(Screen 3), press
to return (Screen 1). Or select “Return” by pressing
and
and press
to go back to the previous screen 1.
>Return
>Preheat Delay
>Prestart Fuel Time
>Cranking Time
Preheat Delay
Screen 3: Press
and move cursor, select the value and press
to modify. Press
to save your modification. Then press
to
return (Screen 2).
0000
0
s
Timers Set
Screen 4: Press
, select and modify the value (it is the same method
as Screen 2 and Screen 3).
>Return
>Preheat Delay
>Prestart Fuel Time
>Cranking Time
Over Shutdown
Screen 5: Set temp. sensor shutdown parameters. Select >Over Shutdown,
press
to enter setting, then press
again to enter Screen 5, press
to select settings, then press
to save and meanwhile the
cursor will move down (as Screen 6).
Enable Choose: Enabled
Set Val: +00098
Delay 00003s
Over Shutdown
Screen 6: Press
to change plus or minus, then press
to
Enable Choose: Enabled