Installation
1.3
GROUND
TERMINAL
GROUND
TERMINALS
COMMUNICATION
TERMINALS
TEST
TERMINALS
+
+
+
1
2 3
4
C
O
M
M
T
E
S
T
Figure 1.3 - Ground Terminal
The
TT301
is protected against reversed polarity.
For convenience there are three ground terminals: one inside the cover and two external, located close
to the conduit entries.
Use of twisted pair (22 AWG) cables is recommended.
Avoid routing signal wiring close to power cables or switching equipment.
The Figure 1.3 shows the correct installation of the conduit, in order to avoid penetration of water, or
other substance, which may cause malfunctioning of the equipment.
CORRECT
WIRES
INCORRECT
Figure 1.4 - Conduit Installation Diagram.
Loop Connections
WARNING
Do
not
connect the Power Supply to the sensor terminals (Terminals 1, 2, 3 and 4).
Connection of the
TT301
working as transmitter should be performed as in Figure 1.6.
CONFIGURATOR
250
Figure 1.5
– Wiring Diagram for the TT301 Working as Transmitter
Connection of the
TT301
working as a controller (Optional) should be as indicated in Figure 1.5.
Summary of Contents for TT301
Page 2: ...www el scada ru...
Page 8: ...TT301 Operation Maintenance Instruction Manual VIII...
Page 16: ...TT301 Operation Maintenance Instruction Manual 1 8...
Page 25: ...Operation 2 9 ALARM 1 ALARM 2 Figure 2 9 Typical Alarm Condition Display...
Page 26: ...TT301 Operation and Maintenance Instruction Manual 2 10...
Page 60: ...TT301 Operation and Maintenance Instruction Manual 5 8...
Page 67: ...Certifications Information A 3 CSA NEMKO and DMT CEPEL...
Page 69: ...Certifications Information A 5 CEPEL...
Page 70: ...Operation and Maintenance Instruction Manual TT301 A 6 Control Drawing Factory Mutual FM...
Page 71: ...Certifications Information A 7 NEMKO...
Page 72: ...Operation and Maintenance Instruction Manual TT301 A 8 Canadian Standards Association CSA...
Page 74: ...SRF Service Request Form B 2...