TT301 - Operation & Maintence Instruction Manual
3.10
1 Step
2
Step
3 Step
4 Step
Get sensor
minimum span
Do Lower
Value = 90 ºC
Do Upper
Value = 0 ºC
100 ºC
Upper Value
90 ºC
Upper Value - Span
0 ºC
Lower Value
Minimum Span = 10 ºC
100 ºC
90 ºC
100 ºC
90 ºC
100 ºC
90 ºC
0 ºC
0 ºC
0 ºC
Do Lower
Value = 100 ºC
Lower Value
Lower Value
Lower Value
Lower Value
Lower Value
st
sd
rd
th
Upper Value
Upper Value
Upper Value
Upper Value
Table
– 3.4 – Procedure to Range without Reference
Calibration With Reference
This is the most convenient way to calibrate a transmitter. Apply the signal for adjusting the 4 mA point
(PV=0 %). The Lower Value is altered but the span remains the same.
The same procedure is applied for the Upper Value.
LOWER VALUE =
0 Ohm
UPPER VALUE =
100 Ohm
Example: When measuring resistance the
TT301
is calibrated as follows:
After the installation is done, the potentiometer (input sensor) was found to have a 5 Ohm residual
resistance when its indicator was on a zero position.
The Lower Value reference trim quickly corrects this problem, causing the Lower Value to equal 5 Ohm.
The Upper Value may be altered in the same way.
As mentioned before, the Ohm or mV sensor input may differ a little from its plant standard.
The Zero and Gain Trim may be used to adjust the transmitter reading to Engineering Units with its
plant standard, thus eliminating possible differences.
Unit
The Engineering Unit shown on the transmitter and the configurator displays may be altered. The units
are linked to a selected process variable.
The following units are available:
- For
mV
input: always mV.
- For
Ohm
input: always
Ohm
.
- For
Thermocouple
and
RTD: Celsius, Fahrenheit, Rankine and Kelvin degrees.
Damping
The
DAMPING
option on the
RANGE
function enables electronic damping adjustment.
The damping may be adjusted between 0 and 32 seconds.
Trim
The TRIM function is used to adjust resistance, voltage and current reading to user standard. To
continue the TRIM adjustment, the control loop must be on MANUAL to avoid disturbances in the
process.
There are two options: Current signal and input reading.
Summary of Contents for TT301
Page 2: ...www el scada ru...
Page 8: ...TT301 Operation Maintenance Instruction Manual VIII...
Page 16: ...TT301 Operation Maintenance Instruction Manual 1 8...
Page 25: ...Operation 2 9 ALARM 1 ALARM 2 Figure 2 9 Typical Alarm Condition Display...
Page 26: ...TT301 Operation and Maintenance Instruction Manual 2 10...
Page 60: ...TT301 Operation and Maintenance Instruction Manual 5 8...
Page 67: ...Certifications Information A 3 CSA NEMKO and DMT CEPEL...
Page 69: ...Certifications Information A 5 CEPEL...
Page 70: ...Operation and Maintenance Instruction Manual TT301 A 6 Control Drawing Factory Mutual FM...
Page 71: ...Certifications Information A 7 NEMKO...
Page 72: ...Operation and Maintenance Instruction Manual TT301 A 8 Canadian Standards Association CSA...
Page 74: ...SRF Service Request Form B 2...