TT301 - Operation and Maintenance Instruction Manual
5.2
DIAGNOSTIC MESSAGES
POTENTIAL SOURCE OF PROBLEM
OUTPUT SATURATED
Primary variable out of calibrated Span (Output current in 3.8 or 20.5
mA, XMTR mode only).
SV OUT OF LIMITS
Temperature out of operating limits.
Temperature sensor damaged.
PV OUT OF LIMITS
Input signal out of operating limits.
Sensor damaged.
Transmitter with false configuration.
PV out of range limits (see table).
Table 1 - Diagnostics with the Configurator
Troubleshooting with Transmitter
Symptom: NO LINE CURRENT
Probable Source of Trouble
:
Transmitter Connections
Check wiring polarity and continuity.
Check for shorts or ground loops.
Power Supply
Check power supply output. The voltage at the
TT301
terminals must be between 12 and 45 Vdc,
and the ripple less than 0.4V.
Electronic Circuit Failure
Check the main board for defect by replacing it with a spare one.
Symptom: NO COMMUNICATION
Probable Source of Trouble
:
Terminal Connections
Check terminal interface connections.
Check if the interface is connected to the points [COMM] and [-] or in the line between the
transmitter and the load resistor.
Check if the interface is model IF2 (for HART Protocol).
Transmitter Connections
Check if connections are as per wiring diagram.
Check line resistance; it must be equal to or greater than 250 Ohm, between the transmitter and the
power supply.
Power Supply
Check output of power supply. The voltage at the
TT301
terminals must be between 12 and 45V,
and ripple less than 0.4V.
Electronic Circuit Failure
Locate the failure by alternately replacing the transmitter circuit and the interface with spare parts.
Transmitter Address
In On Line Multidrop item check if the address is "0".
Summary of Contents for TT301
Page 2: ...www el scada ru...
Page 8: ...TT301 Operation Maintenance Instruction Manual VIII...
Page 16: ...TT301 Operation Maintenance Instruction Manual 1 8...
Page 25: ...Operation 2 9 ALARM 1 ALARM 2 Figure 2 9 Typical Alarm Condition Display...
Page 26: ...TT301 Operation and Maintenance Instruction Manual 2 10...
Page 60: ...TT301 Operation and Maintenance Instruction Manual 5 8...
Page 67: ...Certifications Information A 3 CSA NEMKO and DMT CEPEL...
Page 69: ...Certifications Information A 5 CEPEL...
Page 70: ...Operation and Maintenance Instruction Manual TT301 A 6 Control Drawing Factory Mutual FM...
Page 71: ...Certifications Information A 7 NEMKO...
Page 72: ...Operation and Maintenance Instruction Manual TT301 A 8 Canadian Standards Association CSA...
Page 74: ...SRF Service Request Form B 2...