TT301 - Operation and Maintenance Instruction Manual
4.12
Z:
Moves to the SPAN decrease function.
S:
Decreases the Upper Value (Increases Output) until the magnetic tool is
removed or the minimum for the Upper Value is reached.
Z:
Moves to the SENSOR function.
S:
Increases the Upper Value (Decreases output) until the magnetic tool is
removed or the maximum for the Upper Value is reached.
Reranging using the ZERO and SPAN items in the menu is equivalent to the applied rerange on the
Configurator. The range values are adjusted relative to the applied input. The value in the display is the
applied temperature in percentage of the range. Changing the lower value shifts the upper value too,
maintaining the span. Changing the upper value does not affect the lower value. For example, if you
want 4 mA (0%) for the applied input, adjust until the display reads 0%. Likewise, if you want 20% (7.2
mA), adjust until the display shows 20%.
Sensor (SENS)
Z:
Moves to the OPERATION MODE function.
S:
This function is protected by a "password", when prompted PSWD activate (S) 2
times to proceed with sensor selection.
After activating (S), you can move around the options available in the following table by activating (Z).
SENSOR SELECTION TABLE
DISPLAY
DESCRIPTION
mV-1
-6
to
22 mV
mV-2
-10
to
100 mV
mV-3
-20
to
500 mV
Ohm-1
0
to
100 Ohm
Ohm-2
0
to
400 Ohm
Ohm-3
0
to
2000 Ohm
RTD
RTD
TC
Thermocouple
SPEC
Special Sensor
ESC
- escape -
For all sensors, further selections must be done to determine the specific type and connection. Move
around the available options - listed in the tables below - using (Z).
RTD SELECTION TABLE
DISPLAY
DESCRIPTION
DISPLAY
DESCRIPTION
Cu-10
Cu10
Mi100
MILT Pt100
Ni 120
Ni 120
Mi120
MILT Ni120
I50
IEC Pt50
IE100
IEC751-95 Pt100
I100
IEC Pt100
Go50
GOST Pt50
JI 50
JIS Pt50
Go100
GOST Pt100
JI 100
JIS Pt100
Cu50
GOST Cu50
I500
IEC Pt500
Cu100
GOST Cu100
I1000
IEC Pt1000
Esc
Escape
Summary of Contents for TT301
Page 2: ...www el scada ru...
Page 8: ...TT301 Operation Maintenance Instruction Manual VIII...
Page 16: ...TT301 Operation Maintenance Instruction Manual 1 8...
Page 25: ...Operation 2 9 ALARM 1 ALARM 2 Figure 2 9 Typical Alarm Condition Display...
Page 26: ...TT301 Operation and Maintenance Instruction Manual 2 10...
Page 60: ...TT301 Operation and Maintenance Instruction Manual 5 8...
Page 67: ...Certifications Information A 3 CSA NEMKO and DMT CEPEL...
Page 69: ...Certifications Information A 5 CEPEL...
Page 70: ...Operation and Maintenance Instruction Manual TT301 A 6 Control Drawing Factory Mutual FM...
Page 71: ...Certifications Information A 7 NEMKO...
Page 72: ...Operation and Maintenance Instruction Manual TT301 A 8 Canadian Standards Association CSA...
Page 74: ...SRF Service Request Form B 2...