J-236

KT-502H Series

 

HART protocol 

 

Display rotation in 330 ° range 

 

Better visibility with supporting backlight function 

 

Various inputs (to order, select one from 22 kinds) 

- RTD 8 types 

- Thermocouple 8 types 

- mV 8 types 

- Resistor 2 types 

 

Explosion-proof specification: Ex D IIC T6 

 

Protection structure: IP67 (IEC standard)

Model

KT-502H

Power supply

10.5-45VDC

 (with backlight LCD)

Display method

PV display part

: 7-segment 5-digit (character size: W4×H8mm),

Parameter display part

: 14-segment 8-digit (character size: W2.6×H4.8mm),

52-bar meter

Display range

-19999 to 99999

Setting method

HART-protocol (no setting key)

Response time

1 sec

Input type

RTD

DPt100Ω, DPt500Ω, DPt1000Ω, Ni100Ω, Ni500Ω, Ni1000Ω, Cu50Ω, Cu100Ω

Thermocouple

K, J, T, E, N, S, B, R

Resistance transmission (Ω) 0 - 400Ω, 0 - 2000Ω

Voltage  transmission (mV)

 

10 - 75mV, 

 100 - 100mV,   100 - 500mV,   100 - 2000mV

Output

DC4-20mA (2-wire)

Accuracy

±0.3%

Alarm

Below 3.8mA, Over 20.5mA/Sensor break 3.6mA

Load

Max.(V power supply - 7.5V)/0.22A

Galvanic insulation

2,000VAC (input/output)

Environ- 

ment

Ambient temperature

-20 to 70

storage:

 20 to 80

Ambient humidity

0 to 85%RH, 

storage:

 0 to 85%RH

Explosion class

1

Ex d IIC T6

Protection structure

IP67 (IEC standard)

Material

Body: Aluminum (AlDc.8S), Cover O-Ring: Buna N

Weight

2

Approx. 1.4kg (approx. 1.2kg)

1: The explosion class specification is acquired and managed by KONICS.

※2: 

The weight includes packaging. The weight in parenthesis is for unit only.

Environment resistance is rated at no freezing or condensation.

Item

Description

Mounting bracket

0

Without bracket

1

With bracket

②User temperature range

 

1: To order this unit, write the temperature sensor type and the temperature range.

502H

0

KT

(-270 to 1372, K)

1

Temperature Transmitters with HART Protocol

 Features

 Ordering Information

 Specifications

Please read “Safety Considerations” 

in the instruction manual before using.

Summary of Contents for KT-502H Series

Page 1: ...500mV 100 2000mV Output DC4 20mA 2 wire Accuracy 0 3 Alarm Below 3 8mA Over 20 5mA Sensor break 3 6mA Load Max V power supply 7 5V 0 22A Galvanic insulation 2 000VAC input output Environ ment Ambient temperature 20 to 70 storage 20 to 80 Ambient humidity 0 to 85 RH storage 0 to 85 RH Explosion class 1 Ex d IIC T6 Protection structure IP67 IEC standard Material Body Aluminum AlDc 8S Cover O Ring Bu...

Page 2: ...000 454 to 1832 J Fe CuNi 210 to 1200 346 to 2192 K NiCr Ni 270 to 1372 454 to 2501 6 N NiCrSi NiSi 270 to 1300 454 to 2372 R PtRh13 Pt 50 to 1768 58 to 3214 4 S PtRh10 Pt 50 to 1768 58 to 3214 4 T Cu CuNi 270 to 400 454 to 752 Analog Voltage 10 75mV 100 100mV 100 500mV 100 2000mV Opening cover To open the cover unscrew the M3 6L headless bolt using a 1 5 hexagon wrench and rotate the cover Ø83 14...

Page 3: ...NTER Enter meter Value 4 000 HELP DEL ABORT ENTER Setting fid dev output to 4mA ABORT O K WARN Loop should be removed from automatic control ABORT O K Select the 1 Device Setup by keys and press the key Connect a HART communicator and adjust current trim as below by a HART communicator Select the 2 Diag Service by keys and press the key Select the 4 D A trim by keys and press the key Press the F4 ...

Page 4: ...fications which is reported to Korea Gas Safety Cor poration This unit is manufactured following by the announcement 2013 54 of Ministry of Employment and Labor of Korea Cautions During Use 1 PV LRV 2 URV HELP HOME Select 1 PV LRV Low temperature range and press the key PV LRV 0 000 deg C 0 000 HELP DEL ESC ENTER Set Low temperature range and press the F4 key 1 PV LRV 2 URV HELP HOME Select 2 URV ...

Reviews: