Programming Using Local Adjustment
3.9
Z:
Moves on to function SAVE if the Lower Pressure Trim (LOWER) is running or
to the Upper Pressure Trim (UPPER).
S:
Adjusts the transmitter's internal reference, decreasing the displayed value
that will be interpreted as the Lower Pressure value corresponding to the
applied pressure.
Upper Pressure Trim (UPPER)
Z:
Moves to the decrease upper pressure reading.
S:
Sets the transmitters' internal reference increasing to the value on the display,
which is the reading of the applied pressure.
Z:
Moves to the SAVE function.
S:
Sets the transmitters' internal reference decreasing to the value on de display,
which is the reading of the applied pressure.
Save (SAVE)
Z:
Moves to the ESCAPE from TRIM menu.
S:
Saves the LOWER and UPPER TRIM point in the transmitter EEPROM and
actualize the internal parameters pressure measurement.
Escape (ESC)
Z:
Moves to the ZERO TRIM function.
S:
Escapes to the MAIN menu.
Escape Local Adjustment [ESC]
This branch of the main tree is used to leave the Local Adjustment mode, placing the Transmitter in
the monitoring mode
.
Z:
Selects the OPERATION branch.
S:
Escapes to NORMAL DISPLAY mode, adjusting the
LD290
in monitoring
mode.
Summary of Contents for LD290
Page 1: ......
Page 2: ......
Page 6: ...LD290 Operation and Maintenance Instruction Manual VI...
Page 9: ...Installation 1 3 Figure 1 1 b Dimensional Drawing and Mounting Position for LD290 Sanitary...
Page 11: ...Installation 1 5 Figure 1 1 d Dimensional Drawing and Mounting Position for LD290 Level...
Page 18: ...LD290 Operation and Maintenance Instruction Manual 1 12...
Page 32: ...LD290 Operation and Maintenance Instruction Manual 3 10...
Page 42: ...LD290 Operation and Maintenance Instruction Manual 4 10...
Page 61: ...Appendix A A 7 CEPEL Centro de Pesquisa de Energia El trica...
Page 62: ...LD290 Certifications Information A 8...
Page 63: ...Appendix A A 9 FM Approvals...
Page 64: ...LD290 Certifications Information A 10...
Page 66: ...LD290 Appendix B B 2...