Programming Using Local Adjustment
3.7
Z:
Moves to the DAMPING function.
S:
Decreases the Output in transmitter mode, increases the Upper Pressure
Value until the magnetic tool is removed or the maximum for the Upper Value is
reached.
Damping (DAMP)
Z:
Moves to the DAMPING DECREASE function.
S:
Increases the damping time constant until the magnetic toll is removed or 32
seconds are reached.
Z:
Moves to the SAVE function.
S:
Decreases the damping time constant until the magnetic tool is removed or 0
seconds is reached.
Save (SAVE)
Z:
Moves to the ESCAPE of RANGE menu.
S:
Saves the LRV, URV, ZERO, SPAN and DAMP values in the transmitter
EEPROM.
Escape (ESC)
Z:
Moves to the UNIT function.
S:
Escapes to the ESC function, of the RANGE branch.
Function (FUNCT)
Z:
Moves to the ESCAPE function.
S:
Starts selection of input function. After activating (
S
) you can move around
the available options in the table below by activating (
Z
).
FUNCTIONS
DISPLAY
DESCRIPTION
LINE
Linear to Pressure
TABLE
16 Point Table
ESC
-escape-
Table 3.5 - Functions
The desired function is activated using (
S
). Escape leaves function unchanged.
Summary of Contents for LD290
Page 1: ......
Page 2: ......
Page 6: ...LD290 Operation and Maintenance Instruction Manual VI...
Page 9: ...Installation 1 3 Figure 1 1 b Dimensional Drawing and Mounting Position for LD290 Sanitary...
Page 11: ...Installation 1 5 Figure 1 1 d Dimensional Drawing and Mounting Position for LD290 Level...
Page 18: ...LD290 Operation and Maintenance Instruction Manual 1 12...
Page 32: ...LD290 Operation and Maintenance Instruction Manual 3 10...
Page 42: ...LD290 Operation and Maintenance Instruction Manual 4 10...
Page 61: ...Appendix A A 7 CEPEL Centro de Pesquisa de Energia El trica...
Page 62: ...LD290 Certifications Information A 8...
Page 63: ...Appendix A A 9 FM Approvals...
Page 64: ...LD290 Certifications Information A 10...
Page 66: ...LD290 Appendix B B 2...