Installation
1.7
Observe operating safety rules during wiring, draining or blow-down.
Some examples of installation, illustrating the position of the transmitter in relation to the taps, are
shown in Figure 1.3.
Figure 1.2
– Fixing of the Transmitter in the Tap
GAS
LIQUID
STEAM
Figure 1.3
– Position of the Transmitter and Taps
The location of pressure taps and the relative position of the transmitter are indicated in Table 1.1.
Process Fluid
Location of Taps LOCATION OF LD290 IN RELATION TO THE TAPS
Gas
Top or Side
Above the Taps
Liquid
Side
Below the Taps or at the Piping Centerline
Steam
Side
Below the Taps using Sealing (Condensate) Pots
Table 1.1 - Location of Pressure Taps
NOTE
Except for dry gases, all impulse lines should slope at the ratio 1:10, in order to avoid trapping
bubbles in the case of liquids, or condensate for steam or wet gases.
Summary of Contents for LD290
Page 1: ......
Page 2: ......
Page 6: ...LD290 Operation and Maintenance Instruction Manual VI...
Page 9: ...Installation 1 3 Figure 1 1 b Dimensional Drawing and Mounting Position for LD290 Sanitary...
Page 11: ...Installation 1 5 Figure 1 1 d Dimensional Drawing and Mounting Position for LD290 Level...
Page 18: ...LD290 Operation and Maintenance Instruction Manual 1 12...
Page 32: ...LD290 Operation and Maintenance Instruction Manual 3 10...
Page 42: ...LD290 Operation and Maintenance Instruction Manual 4 10...
Page 61: ...Appendix A A 7 CEPEL Centro de Pesquisa de Energia El trica...
Page 62: ...LD290 Certifications Information A 8...
Page 63: ...Appendix A A 9 FM Approvals...
Page 64: ...LD290 Certifications Information A 10...
Page 66: ...LD290 Appendix B B 2...