Parameter Lists
SMA Solar Technology AG
148
SBU2200-TEN083320
Technical Description
20.3 Diagnostics
310# Diag Inverter
320# Diag Battery
Menu
no.
Parame
ter no.
Parameter name
Range/unit
Description
311# Diag Total
311
01
EgyCntIn
kWh
energy absorbed
311
02
EgyCntOut
kWh
energy fed
311
03
EgyCntTm
h
energy metering run time
312# Diag Device
312
01
Adr
Master
device address (type)
312
02
FwVer
BFR firmware version
312
03
SN
serial number
312
04
OnTmh
h
operating hours
312
06
OpStt
Operating
Warning
Failure
operating mode (device)
312
07
CardStt
Off
Operational
Mount
OutOfSpace
BadFileSys
Incomp
Parameter
ParamFailed
WriteLogData
WriteLogFailed
MMC/SD card status message:
= no Sunny Backup 2200
= in operation
= card initializing
= insufficient memory capacity (on card or in main
directory)
= incorrect file system
= incompatible card
= parameter update is active
= error during parameter update
= writing log data to card
= error upon writing log data to card
312
08
FwVer2
DSP firmware version
312
09
FwVer3
BFR boot loader
312
10
FwVer4
DSP boot loader
Menu
no.
Parame
ter no.
Parameter name
Range/unit
Description
320
01
Soh
%
state of health (SOH), ratio of current capacity and
nominal value
320
02
StatTm
d
statistics metering run time
320
03
ChrgFact
charging factor
320
04
BatEgyCntIn
kWh
energy meter for battery charge