Parameter Lists
SMA Solar Technology AG
142
SBU2200-TEN083320
Technical Description
20.2 Adjustable System Parameters
210# Set Inverter
220# Set Battery
NOTICE!
Damage caused by incorrect values.
Once the button is pressed, operating data values can immediately change to their new
settings. Incorrect values in these parameters can probably not be corrected quickly
enough.
• Only qualified electricians are permitted to set and adjust system parameters.
• Parameters marked with
(Stby)
are to be changed only when the inverter is in
standby mode.
Parameter changes
All menu items that can only be changed after entering the installer password are shaded
in gray in the following tables.
All parameters can be set using a connected PC/laptop with the Sunny Data Control
software, a Sunny WebBox or a Sunny Boy Control (see section 7.5 „Communication“
(61)).
Menu
no.
Parame
ter no.
Parameter name
Range/unit
Default
value
Description
210
01
InvVtgNom
V
230
nominal inverter voltage
210
02
InvChrgCurMax
A
9.6
maximum AC charging current
210
03
InvFrqNom
Hz
50
nominal inverter frequency:
210
04
InvVtgMin
V
172.5
minimum inverter voltage:
210
05
InvVtgMax
V
264.5
maximum inverter voltage:
210
06
InvFrqMin
Hz
40
minimum inverter frequency
210
07
InvFrqMax
Hz
70
maximum inverter frequency
Menu
no.
Parame
ter no.
Parameter name
Range/unit
Default
value
Description
221# Bat Property
221
01
BatTyp
VRLA
FLA
NiCd
VRLA
battery type:
= valve regulated lead acid
= flooded lead acid
= nickel cadmium
can only be changed in QCG
221
02
BatCpyNom
Ah
140
Nominal battery capacity (E:C10/U:C20)
221
03
BatVtgNom
V
24
nominal battery voltage