background image

Troubleshooting Guide

7

Solenoid Screen Filter Cleaning Procedure

A

Turn off water supply at supply stop(s). Activate Faucet to relieve
system pressure.

B

Remove Water Supply Line from Inlet Side of Solenoid Valve. Remove
Cap, Water Line Fitting, Gasket, Filter Housing and Filter from Solenoid
Valve Housing.

C

Slide Filter off Filter Housing. Clean Filter using fresh tap water only. If
necessary, use a small brush to clean. Use caution while cleaning to
prevent damage to Filter.

If any Filter components are damaged, replace as necessary. Examine
the Gasket for wear or damage; replace if necessary.

D

Reinstall Filter on Filter Housing.

Install Filter Housing, Gasket, Water Line Fitting and Cap onto Solenoid
Valve Housing.

Tighten Cap securely. 

FILTER

E

Reinstall Water supply Line to Inlet Side of Solenoid Valve.

INLET SIDE OF SOLENOID VALVE HOUSING

FILTER HOUSING

WATER LINE FITTING

GASKET

CAP

When assistance is required, please contact your local Sloan
Representative or Sloan Valve Company Installation Engineering
Department at:

1-888-SLOAN-14 (1-888-756-2614)

1. PROBLEM: Sensor LED does not function (indicator light on sensor window

in faucet spout does not flash during initial 10 minute set-up
mode).

CAUSE: There is no visible indicator light. Normal operation.

SOLUTION: This is a normal operating feature of the faucet.

2. PROBLEM: Faucet does not deliver any water when Sensor is activated.

INDICATOR: Solenoid valve produces audible “CLICK.”

CAUSE: Water supply stop(s) closed.

SOLUTION: Open supply stop(s) completely.

INDICATOR: Solenoid valve DOES NOT produce an audible “CLICK.”

CAUSE: Solenoid Lead is not properly connected to the Control Module.

SOLUTION: Disconnect and reconnect Solenoid Lead to the Control Module.

CAUSE: No battery or Transformer (optional) power is being supplied to

Sensor.

SOLUTION: Ensure  that  the  batteries  are  installed  properly.  Check  that  the

orientation of each battery matches the positive (+) and negative
(—) symbols shown on the bottom of the battery compartment.
Reinsert  the  Batteries  into  the  Control  Module.    Transformer
(optional) is unplugged or wall receptacle has no power.

CAUSE: Sensor Cable is not properly connected to the Control Module.

SOLUTION: Disconnect and reconnect Sensor Cable to the Control Module.

CAUSE: Sensor range is set at minimum distance.

SOLUTION: Increase Sensor range. Refer to Step 9, Range Adjustment.

CAUSE: Control Module assembly is defective.

SOLUTION: Replace Control Module assembly.

3. PROBLEM: Faucet delivers only a slow flow or dribble when Sensor is

activated.

CAUSE: Water supply stop(s) partially closed.

SOLUTION: Open supply stop(s) completely.

CAUSE: Solenoid Filter is clogged.

SOLUTION: Remove, clean and reinstall Filter. Refer to Solenoid Screen Filter

Cleaning Procedure on Page 6. Replace with new Solenoid Filter
Kit if necessary.

CAUSE: Aerator is clogged.

SOLUTION: Remove, clean and reinstall Aerator.

4. PROBLEM: Faucet does not stop delivering water or continues to drip after

user is no longer detected (automatic shut-off fails even when
batteries are removed).

CAUSE: Solenoid Valve has been connected backwards.

SOLUTION: Disconnect Solenoid Valve compression fittings at both the inlet

and outlet positions. The water should flow from inlet through the
Solenoid  Valve  to  the  outlet  according  to  the  direction  of  the
arrow  shown  on  the  side  of  the  Solenoid Valve.  Reconnect  the
compression fittings in the correct orientation.

CAUSE: Solenoid Valve is dirty.

SOLUTION: Backflush  by  reversing  water  flow  (opposite  to  the  direction

shown by the arrow on the side of the Solenoid Valve) through
the  Solenoid  Valve.  Reconnect  the  compression  fittings  in  the
correct orientation. Activate faucet.

CAUSE: Solenoid Valve Module is defective.

SOLUTION: Replace Solenoid Valve Module.

5. PROBLEM: The water temperature is too hot or too cold on a faucet

connected to hot and cold supply lines with Bak-Chek Tee.

CAUSE: Supply stops are not adjusted properly.

SOLUTION: Adjust supply stops.

NOTE:

For some systems, a Thermostatic Mixing Valve may be required.

6. PROBLEM: The Red LED turns on in the control module (below deck).

CAUSE: One (or more) of the batteries is “dead.” 

SOLUTION: To ensure proper operation, insert four (4) new AA-size Alkaline

batteries. Check that the orientation of each battery matches the
positive (+) and negative (—) symbols shown on the bottom of
the  battery  compartment.  Reinsert  Batteries  into  the  Control
Module.

CONTROL

MODULE

ENCLOSURE

FROM SOLENOID VALVE

FROM OPTIONAL

ADAPTER

STRAIN

RELIEF
SLOTS

FROM FAUCET SPOUT

POWER CABLE

JACK

MODULAR

RECEPTACLE

LOCKING

CONNECTOR

Summary of Contents for Optima ETF-600

Page 1: ...f 15 VA of current rating for each solenoid valve used Refer to Step 4 Install Transformer for further information Mixing Valve When installing the faucet with a Sloan mixing valve these Installation...

Page 2: ...ASE GASKET Note Refer to the Installation Instructions included with the ETF 578 A Trim Plate for additional information about using an 8 Trim Plate with an ETF 600 faucet Apply thread sealant or Tefl...

Page 3: ...PLY SOLENOID VALVE 1 4 PIPE TO 3 8 TUBE COMPRESSION FITTING 3 8 SUPPLY TUBE NOT SUPPLIED 3 8 BAK CHEK COMPRESSION TEE FOR APPLICATIONS USING DUAL WATER SUPPLY ETF 600 ETF 610 3 8 10 mm SUPPLY TUBE 3 8...

Page 4: ...ommended A Run wires from secondary side of Transformer to 3 8 inch 10 mm hole at back of Control Module Enclosure If necessary wires can be run through wall and then inserted through hole in back of...

Page 5: ...NAL BLOCK 2 INSERT POWER CABLES 3 SECURE WITH SCREWS 4 REINSTALL TERMINAL BLOCK CONNECTOR BOARD POWER CABLE MODULAR RECEPTACLE B Insert Solenoid Valve Connector into the Modular Receptacle on Connecto...

Page 6: ...3 Dip Switches as shown in Table 1 Table 1 Time Out Settings Unless otherwise specified all ETF 600 ETF 610 Faucets leave the factory set with a 30 second Time Out Note The position of Dip Switch 4 ra...

Page 7: ...ates BUT does NOT change to RED when hands are placed in the Sensor s detection zone CAUSE Sensor range is set too short SOLUTION Increase Sensor detection range CAUSE Sensor is faulty SOLUTION Replac...

Page 8: ...Strain Relief and Crimp Connectors Transformer to Control Module OPTIONAL TRIM PLATES 13A ETF 607 A 4 102 mm Centerset Single hole Trim Plate Kit for ETF 610 Faucet 13B ETF 608 A 8 203 mm Centerset S...

Page 9: ...supply lines or tempered water supply line Mixing Valve When installing the faucet with a Sloan Mixing Valve these Installation Instructions AND the Installation Instructions packaged with the Mixing...

Page 10: ...lves for Hot and Cold Water Supply shown with 4 trim Plate ADAPTER OPTIONAL ADAPTER OPTIONAL ADAPTER OPTIONAL ADAPTER OPTIONAL ADAPTE OPTIONA ADAPTER OPTIONAL ADAPTER OPTIONAL ADAPTER OPTIONAL ADAPTER...

Page 11: ...old supply stops Supply tubes and stops furnished by installer Install a 3 8 inch 10 mm copper supply tube between Bak Chek Compression Tee and inlet side of Solenoid Valve Tighten Compression Fitting...

Page 12: ...and Plastic Anchors A Install the Control Module in an appropriate location Control Module must be installed so that all cables enter from the bottom of the unit When installed Cables from the Spout a...

Page 13: ...ts are factory set to operate when hands are placed 4 to 5 inches 102 to 127 mm from Sensor This range should be satisfactory for most installations If range adjustment is required refer to the follow...

Page 14: ...ative finishes Use ONLY soap and water then wipe dry with clean cloth or towel While cleaning the bathroom tile the faucet should be protected from any splattering of cleaner Acids and cleaning fluids...

Page 15: ...Module SOLUTION Disconnect and reconnect Sensor Cable to the Control Module CAUSE Sensor range is set at minimum distance SOLUTION Increase Sensor range Refer to Step 9 Range Adjustment CAUSE Control...

Page 16: ...ludes Base Gasket Spacer Washer 9 16 Lockwasher 1 4 NPSM Hex Nut and ETF 547 Compression Fitting Connector 5 ETF 547 1 8 NPT Pipe to 3 8 Tube Compression Fitting Connector female 6 ETF 617 A 3 8 Bak C...

Page 17: ...ide when installing the Sloan EBF 625 or EBF 655 faucet as always good safety practices and care when installing your new faucet if further assistance is required contact your nearest Sloan representa...

Page 18: ...NG 3 8 COMPRESSION FITTING 3 8 COPPER SUPPLY TUBE NOT SUPPLIED 3 8 COPPER SUPPLY TUBE NOT SUPPLIED SOLENOID VALVE EBF 655 FAUCET WITH SINGLE LINE WATER SUPPLY EBF 625 FAUCET WITH SINGLE LINE WATER SUP...

Page 19: ...hen connecting the faucet to a hot and cold water supply two Bak Cheks are required water temperature can be con trolled by adjusting the supply stops when connecting the faucet to a single line water...

Page 20: ...so that it faces sideways vertically however optimum performance is obtained when the control module is horizontal with the Sloan logo on the cover facing up install the control module in an appropri...

Page 21: ...UBE COMPRESSION FITTING 1 8 PIPE NIPPLE 3 8 SUPPLY TUBE NOT SUPPLIED SOLENOID VALVE 3 8 TEE COMPRESSION FITTING 3 8 SUPPLY TUBE NOT SUPPLIED 3 8 SOLENOID VALVE COMPRESSION FITTING TOP OUTLET 3 8 SOLEN...

Page 22: ...T The opTima plus EBF 625 and EBF 655 faucets are factory set to operate when hands are placed 4 5 102 127 mm from sensor This range should be satisfactory for most installations if range adjustment i...

Page 23: ...the faucet to purge any air from the system lines Check for leaks and repair as necessary OPERATION 1 a continuous invisible beam of infrared light is emitted from the sensor located on the throat of...

Page 24: ...plied to sensor Ensure that the batteries are installed properly Check that the orientation of each battery matches the positive and negative symbols shown on the bottom of the battery compartment rei...

Reviews: