Factory settings for parameters
Programming steps
Factory setting
Description
P1
Pause time – 0 to 59 hours
00
Pause time – 0 to 59 minutes
NO
Output of both fault relays
NO (normally open)
NC (normally closed)
02
Two options for signalling a fault
o1 (Option 1)
F1 relay contact
a) Low-level fault will cause F1 contact to repeatedly open and close.
b) Pressure fault will cause F1 contact to close and stay closed.
F2 relay contact
Low-level fault or pressure fault will cause F2 contact to close and stay closed.
o2 (Option 2)
F1 fault relay’s contact will close on a low-level fault
F2 fault relay’s contact will close on a pressure fault
Both contacts can be used for remote signalling.
SP
Option to have pump start with pause time or lube cycle.
SP – Pump starts with a pause time
SO – Pump starts with a lube cycle
35
P7
programming step will only appear on pump with internal pressure transducer. (Reading x 100)
35 x 100 = 3 500 psi. 3 500 psi
(241 bar)
is maximum pressure that pump will build. Adjustable
from 1 400 to 4 600 psi
(96 to 317 bar)
in 100 psi
(6,9 bar)
increments.
09
P8
programming step will only appear on pump with external pressure transducer.
(Reading x 100) 09 x 100 = 900 psi. 900 psi
(62 bar)
is where = external pressure transducer will
open (vent) adjustable from 200 to 1 000 psi
(13 to 69 bar)
in 100 psi
(6,9 bar)
increments.
22