SJE-Rhombus VFDC-4100 Controller User Manual
2.3 Default Values
Menus
Setup Menus
Default
Input Range
YEAR
2004
0000 ~ 9999
MONTH
1
1 ~ 12
DATE
1
1 ~ 31
DATE
WEEKDAY
0
MONDAY ~ SUNDAY
TIME
HOUR
0
0 ~ 23
MINUTE
0
0 ~ 59
SECOND
0
0 ~ 59
LEAD PUMP
PUMP 1
1 ~ 4
PUMP 1
USED
USED, NOT USED, JOCKEY
PUMP
PUMP 2
USED
USED, NOT USED
SET UP
PUMP 3
NOT USED
USED, NOT USED
PUMP 4
NOT USED
USED, NOT USED
SET PRESSURE
60 PSI
2 PSI ~ 650 PSI
SET PRESSURE 2
60 PSI
2 PSI ~ 650 PSI
HIGH PRESSURE LIMIT
95 PSI
3 PSI ~ 719 PSI
PRESSURE
LOW PRESSURE LIMIT
15 PSI
1 PSI ~ 649 PSI
SET UP
START LEAD PRESSURE
-3 PSI
-65 PSI ~ 65 PSI
START LAG PRESSURE
-7 PSI
-65 PSI ~ 65 PSI
STOP LAG PRESSURE
3 PSI
-0 PSI ~ 65 PSI
P VALUE
60
0 ~ 200
I VALUE
30
0 ~ 200
D VALUE
1
0 ~ 200
CYCLE TIME
120 Msec.
50 ~ 999 M.SEC.
ALTERNATION
24 HOURS
0 ~ 999 HOURS
FRICTION
0.0 PSI
0 ~ 650 PSI
CONTROL
RUN DELAY
1 SECONDS
0 ~ 10 SECONDS
SET UP
STOP DELAY
1 SECONDS
0 ~ 999 SECONDS
JOCKEY STOP DELAY
5 SECONDS
0 ~ 999 SECONDS
OPERATION TYPE
VFD
VFD, 1VFD+ATL
LOW SUCTION TMR
30 SECONDS
10 ~ 999 SECONDS
LOW SUCTION RST
AUTO
AUTO, MANUAL
LOW SUCTION RST TMR
30 SECONDS
10 ~ 9999 SECONDS (2.78 HOURS)
LOW PRESSURE STOP TIME
10 SECONDS
10 ~ 999 SECONDS
INITIALIZE
YES,
NO
SENSOR
SENSOR VALUE
200 PSI
29 PSI ~ 720 PSI
SET UP
SENSOR OFFSET
0 PSI
-72 PSI ~ 72 PSI
VFD STOP TIME
30 SECONDS
0 ~ 60 SECONDS
VFD MINIMUM RATE
40%
10 ~ 90 % (of VFD DISP. TYPE)
VFD STOP RATE
60%
20 ~ 90 (of VDF DISP. TYPE)
VFD
VFD DISP. TYPE
100%
100%, 60Hz, 50Hz
VFD AUTO RESET
5
0 ~ 20
PIPE FILL
OFF
ON, OFF
PIPE FULL RATE
45%
10 ~ 90% of VFD DISP. TYPE or VFD
PIPE FILL TIMER
30 SECONDS
5 ~ 600 SECONDS