SJE-Rhombus VFDC-4100 Controller User Manual
7
2.3 Default Values con’t.
Menus
Setup Menus
Default
Input Range
IDLE PREVENTION
NOT USED
USED, NOT USED
PROTECT
FREEZE PREVENTION
NOT USED
USED, NOT USED
PASSWORD USE
NOT USED
USED, NOT USED
PASSWORD
1234
0000 ~ 9999
RETURN TO MAIN SCREEN
120 SECONDS
10 ~ 300 SECONDS
LCD BACK LIGHT TIME
120 SECONDS
10 ~ 998 SECONDS (999 TO DISABLE)
DATA LOG
60 SECONDS
0 ~ 999 SECONDS (16.65 MIN)
TEST CODE
0
0 ~ 9999 (NOT USED)
RELAY OUTPUT 1
STOP
AVAILABLE SETTINGS FOR OUTPUTS:
RELAY OUTPUT 2
RUNNING
NOT USED, PUMPS STOPPED, PUMPING,
SYSTEM
RELAY OUTPUT 3
ALARM
GENERAL ALARM, LOW SUCTION, P1-P4
RELAY OUTPUT 4
NOT USED
VFD RUN, P1-P4 ALT RUN, BUZZER,
RELAY OUTPUT 5
NOT USED
LOW PRESSURE, HIGH PRESSURE,
DIGITAL OUTPUT 6~13
NOT USED
VFD1-4 FLT/HOA, SENSOR FAULT
LANGUAGE
ENGLISH
ENGLISH,
ESPANOL
PRESSURE UNIT
PSI
PSI, BAR
SCHEDULE OPERATION
NOT USED
NOT USED, TIMELY, WEEKLY, MONTHLY
PROGRAM
00:00:00~00:00:00
NOT USED
0 PSI ~ 650 PSI
TUESDAY
NOT USED
0 PSI ~ 650 PSI
FEBRUARY
NOT USED
0 PSI ~ 650 PSI
PARITY
NONE
EVEN, ODD, NONE
BAUDRATE
9600
9600, 14400, 19200
COMM
NODE
1
1~31
SET
DATA
BITS
8
STOP
BIT
1
1,2
ALARM DATA
32 MOST RECONT ALARMS SAVED
SEE CHAPTER 6
OPERA DA
OPERATION DATA SELECTION
RUN LOG
RUN LOG, PUMP RUN TIMES
Total 2000 lines of data saved.
(Refer to Chapter 6)