SJE-Rhombus VFDC-4100 Controller User Manual

3.2.6  VFD Setup

  Menus 

Setup Menu 

Contents 

Input Range

 

 

VFD STOP TIME 

Time delay for when the last pump stops after 

0 ~ 60 SECONDS 

 

 

 

 

the speed drops to the VFD minimum rate. 

   

 

 

 

 

VFD MINIMUM RATE 

VFD minimum speed output 

10 ~ 90%

 

 

VFD STOP RATE 

The last pump stops when its speed is less than 

20 ~ 90%   

 

 

 

 

this set value and the VFD STOP TIME is done.

 

 

VFD DISP. TYPE 

Display the VFD output value on the main screen. 

100%, 60Hz, 50Hz

 

VFD  

VFD AUTO RESET 

Reset times after an alarm happened while the  

0 ~ 20 

 

 

 

 

 

VFD was operating.

 

 

PIPE FILL 

Enable or disable the pipe fill function. 

ON, OFF 

 

 

 

 

PIPE FILL RATE 

The preset speed the pump will run on start up 

10- 90% or VFD min speed 

 

 

 

slowly fill the pipes. Runs for the PIPE FILL 

   

 

 

 

 

 

TIMER or the SET PRESSURE is reached. 

   

 

 

 

 

PIPE FILL TIMER 

The length of time the pump will run. If the set 

5 ~ 600 SECONDS   

 

 

 

pressure is reached during this time, the  

   

 

 

 

 

 

system will switch to PID immediately.

3.2.7  Protect Setup

  Menus 

Setup Menu 

Contents 

Input Range

 

 

IDLE PREVENTION 

When set to USED, if the lead pump has not ran 

USED, NOT USED   

 

 

 

for 10 days, the system will automatically run the 

   

 

 

 

 

 

lead pump at the minimum operating speed for 60 

   

 

 

 

 

 

seconds. Then it will switch lead pump. The same 

   

 

 

 

 

 

process will be repeated if the succeeding lead 

   

 

 

 

 

 

pump does not run for 10 days etc. 

   

 

PROTECT 

FREEZE PREVENTION 

When set to USED, the lead pump will automatically  USED, NOT USED   

 

 

 

start the VFD minimum output for 30 seconds and 

   

 

 

 

 

 

then shift to the next pump when the temperature 

   

 

 

 

 

 

is under 32 deg. This will occur when all pumps are 

   

 

 

 

 

 

stopped for more than 30 seconds at the same time

 

 

PASSWORD USE 

See password section for description 

USED, NOT USED   

 

 

PASSWORD 

 

0000 ~ 9999

3.2.5  Sensor Setup

  Menus 

Setup Menu 

Contents 

Input Range

 

SENSOR 

TRANSDUCER TYPE 

Range Setup of Sensor 

29 PSI ~ 720 PSI 

 

 

SETUP 

SENSOR ADJUST 

Sensor Offset Value 

-72 PSI ~ 72 PSI

Summary of Contents for VFDC-4100

Page 1: ...ecifically designed for Pressure Booster Pump Systems The VFDC 4100 controller is capable of maintaining a constant discharge pressure by adjusting the speed of up to 4 Variable Frequency Drives VFDs one VFD and up to 3 across the line ATL starters or one Jockey pump and up to 3 main pumps ...

Page 2: ... before installing or servicing this product A qualified service person must install and service this product according to applicable electrical codes and electrical schematics EXPLOSION OR FIRE HAZARD Do not use this product with flammable liquids Do not install in hazardous locations as defined by National Electrical Code ANSI NFPA 70 Do not install in area with excessive or conductive dust corr...

Page 3: ...3 1 Security 10 3 2 Details of Setup Menus 10 3 3 Setup Menu Display Input Method 14 Chapter 4 4 1 Triplex VFD Power Circuit Schematic VFD 16 4 2 Triplex Controller Circuit Schematic VFD 17 4 3 Triplex VFD Power Circuit Schematic 1VFD ATL 18 4 4 Triplex Controller Circuit Schematic 1VFD ATL 19 Chapter 5 5 1 Troubleshooting 20 Chapter 6 6 1 Fault Alarm Display Corrective Actions 21 6 2 Alarm Data S...

Page 4: ... 1 1 1 Controller Description Front View Rear View LCD Screen LED Indicators Push Buttons CN2 Sensor Terminal CN10 COMM Port CN7 Fault Inputs CN8 Low Suction Set Pressure 2 CN1 Annalog Speed Refs CN3 Transistor outputs CN5 Relay outputs CN4 DC Input Power ...

Page 5: ...SJE Rhombus VFDC 4100 Controller User Manual 3 1 2 Controller Outline Dimensions in inches ...

Page 6: ...n the total operating time of the lead pump reaches to the alternation time the system automatically selects the next pump in sequence to be the lead pump This function is designed to reduce the system life cycle cost The system make all pump operate for equal period of time as to prevent the over use of a particular pump resulting in high parts wear of the pump The alternation may also be cycle b...

Page 7: ...ows for maximum life span of the LCD monitor This function can be disabled if desired Jockey Pump Function The role of the Jockey pump is to maintain constant pressure during low flow conditions When utilized the jockey pump is typically much smaller than the main pumps and is well suited to handle variations in flow at a low flow rate When flow demand exceeds the capacity of the Jockey pump and t...

Page 8: ...E 60 0 200 I VALUE 30 0 200 D VALUE 1 0 200 CYCLE TIME 120 Msec 50 999 M SEC ALTERNATION 24 HOURS 0 999 HOURS FRICTION 0 0 PSI 0 650 PSI CONTROL RUN DELAY 1 SECONDS 0 10 SECONDS SET UP STOP DELAY 1 SECONDS 0 999 SECONDS JOCKEY STOP DELAY 5 SECONDS 0 999 SECONDS OPERATION TYPE VFD VFD 1VFD ATL LOW SUCTION TMR 30 SECONDS 10 999 SECONDS LOW SUCTION RST AUTO AUTO MANUAL LOW SUCTION RST TMR 30 SECONDS ...

Page 9: ...PED PUMPING SYSTEM RELAY OUTPUT 3 ALARM GENERAL ALARM LOW SUCTION P1 P4 RELAY OUTPUT 4 NOT USED VFD RUN P1 P4 ALT RUN BUZZER RELAY OUTPUT 5 NOT USED LOW PRESSURE HIGH PRESSURE DIGITAL OUTPUT 6 13 NOT USED VFD1 4 FLT HOA SENSOR FAULT LANGUAGE ENGLISH ENGLISH ESPANOL PRESSURE UNIT PSI PSI BAR SCHEDULE OPERATION NOT USED NOT USED TIMELY WEEKLY MONTHLY PROGRAM 00 00 00 00 00 00 NOT USED 0 PSI 650 PSI ...

Page 10: ...s The system will ask for a password if enabled Using the arrow buttons navigate to the item desired and press enter Navigate with the arrows and enter the item of choice to display its value Enter to change the value using the arrow buttons and again press the enter button to accept the new value or press esc to exit without saving Press the esc enter and arrow buttons as desired to move up drill...

Page 11: ...TO selector switches in AUTO position Input CN7 STOP is displayed if none of the HAND OFF AUTO selector switches are in AUTO position 4 VFD Output Frequency Display Display of the output value of the VFD running The VFD output display can be configured in percentage or in frequency 50Hz or 60Hz 5 Pump Status Display Idle Running VFD Fault or Jockey 6 Pump Number Display of the total pumps and Lead...

Page 12: ...e is disabled by default INPUT PASSWORD 0 0 0 0 04 12 01 Ver 1 03 3 2 Details of Setup Menus 3 2 1 Date Time Setup Current Time Setup Menus Setup Menu Contents Input Range YEAR Current Year Display 0000 9999 MONTH Current Month Display 1 12 DATE Current Date Display 1 31 DATE TIME DAY Current Day Display MONDAY SUNDAY HOUR Current Hour Display 0 23 MINUTE Current Minute Display 0 59 SECOND Current...

Page 13: ...current pressure is over 63 PSI 3 2 4 Control Setup Menus Setup Menu Contents Input Range P P Value Setup of PID Proportional 0 200 I I Value Setup of PID Integral 0 200 D D Value Setup of PID Derivative 0 200 CYCLE TIME Sampling time of PID Control 0 999 m sec ALTERNATION Shifts the lead to the next available pump in the 0 999 HOURS set to 0 for sequence lead Change every cycle set to 999 for no ...

Page 14: ...ll run If the set 5 600 SECONDS pressure is reached during this time the system will switch to PID immediately 3 2 7 Protect Setup Menus Setup Menu Contents Input Range IDLE PREVENTION When set to USED if the lead pump has not ran USED NOT USED for 10 days the system will automatically run the lead pump at the minimum operating speed for 60 seconds Then it will switch lead pump The same process wi...

Page 15: ...S STOPPED PUMPING GENERAL ALARM LOW SUCTION P1 P4 VFD RUN P1 P4 ATL RUN BUZZER LOW PRESSURE HIGH PRESSURE VFD 1 4 FLT HOA SENSOR FAULT LANGUAGE Language selection English Espanol PRESS UNIT Unit of measure for analog input PSI BAR 3 2 9 Communication Setup RS 485 Menus Setup Menu Contents Input Range PARITY Select parity mode EVEN ODD NONE COMM BAUDRATE Transmission speed 9600 14400 19200 SETUP NO...

Page 16: ...me on the Menu Setup Fig 1 2 Moved to the set position which needs to be changed Year Month Day Week by Right Left key Press the Enter key and edit when flashing 3 Change the value by using the Up Down keys 4 Save the changed value by pressing the Enter key 5 Exit to the main screen by pressing the ESC key DATE TIME PUMP SET PRESSURE CONTROL SENSOR VFD PROTECT SYSTEM PROGRAM COMM SET ALARMS DATA L...

Page 17: ...T ALARMS DATA LOG PRESSURE SETUP 60 0 RUN SET PRESSURE 60 PSI HIGH PRE LIMIT 150 PSI LOW PRE LIMIT 20 PSI Press the MENU button Use the UP DOWN and RIGHT LEFT keys to go to the Pressure Menu Press ENTER button to open the Pressure Menu Moved to the set position which needs to be changed using the UP DOWN key Press ENTER key Use the UP DOWN and RIGHT LEFT keys to edit Save the changed value by pres...

Page 18: ...16 SJE Rhombus VFDC 4100 Controller User Manual Chapter 4 4 1 Typical Triplex VFD Power Circuit Schematic OPER TYPE VFD ...

Page 19: ...SJE Rhombus VFDC 4100 Controller User Manual 17 RS 485 CN10 4 2 Typical Triplex Controller Circuit Schematic OPER TYPE VFD ...

Page 20: ...4 3 Typical Triplex VFD Power Circuit Schematic OPER TYPE 1VFD ATL 18 SJE Rhombus VFDC 4100 Controller User Manual ...

Page 21: ...SJE Rhombus VFDC 4100 Controller User Manual 19 4 4 Typical Triplex Contorller Circuit Schematic OPER TYPE 1VFD ATL RS 485 CN10 ...

Page 22: ...o transducer replace if necessary Check valve back flow Consult your mechanical contractor Abnormal air pressure tank Consult your mechanical contractor Insufficient pressure tank capacity Consult your mechanical contractor Abnormal voltage Check the voltage Defective motor Consult your mechanical contractor The pump is broken Consult your mechanical contractor The infiltration of foreign object i...

Page 23: ...witch optional on suction piping present while the system was operating Reset If LOW SUCTION RST is set to MANUAL the RESET button must be pressed to clear the alarm If set to AUTO the alarm will clear itself based on the LOW SUCTION RST TMR Output LCD Display ERROR LED BUZZER Actions Please check the suction pressure piping low water level wiring and change the low water level sensor The system w...

Page 24: ... DOWN and RIGHT LEFT keys to go to the Data Log Menu Press ENTER button to open the Data Log Menu Menu Setup Screen Use the or keys to select between OPERA DATA RUN TIME Enter to display 6 2 Alarm Data Screen Alarm Data Screen View Acknowledgement Method The system is able to record total 32 data Records and displays the alarm sequentially by Number Date Alarm Occur times and alarm type UP DOWN KE...

Page 25: ...4 43 33 0 0 1P 0 I1E VFD 1 Error 12 23 14 43 33 0 0 1P 0 I2E VFD 2 Error 12 23 14 43 33 0 0 1P 0 I3E VFD 3 Error 12 23 14 43 33 0 0 1P 0 I4E VFD 4 Error 12 23 14 43 33 0 0 1P 0 LPS Low Pressure Stop 12 23 14 43 33 0 0 1P 0 Sop Sensor Open 12 23 14 43 33 0 0 1P 0 Sap Sensor Shortage 12 23 14 43 33 0 0 1P 0 LWS Low Water StopRecords when power is supplied Displays as 12 23 14 43 33 0 0 1P 0 Pun Reco...

Page 26: ... 002 low pressure R 004 VFD1 fault HOA R 008 VFD2 fault HOA R 016 VFD3 fault HOA R 032 VFD4 fault HOA R 064 low water alarm R 128 low pressure alarm R 256 sensor open R 512 sensor short R 1024 low water stop Time setup 1 year R 8001 32 769 2xxxx 2 month R 8002 32 770 xx 3 day R 8003 32 771 xx 4 week R 8004 32 772 xx 5 hour R 8005 32 773 xx 6 min R 8006 32 774 xx 7 sec R 8007 32 775 xx Pump setup 1...

Page 27: ...just R 8402 33 794 sensor adjust VFD setup 1 VFD stop time R 8501 34 049 sec 2 VFD minimum rate R 8502 34 050 3 VFD stop rate R 8503 34 051 4 VFD display type R 8504 34 052 5 VFD auto rest R 8505 34 053 no Protection setup 1 freeze prevention R 8601 34 305 0 not used 1 used 2 fix prevention R 8602 34 306 0 not used 1 used 3 password use R 8603 34 307 0 not used 1 used 4 password R 8604 34 308 0 not...

Page 28: ... allow limitations on how long an implied warranty lasts so the above limitation may not apply to you Some states do not allow the exclusion or limitation of incidental or conse quential damages so the above limitation or exclusion may not apply to you This warranty gives you specific legal rights and you may also have other rights which vary from state to state TO OBTAIN WARRANTY SERVICE The cons...

Page 29: ..._______________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ _____________________________________________________________________________...

Page 30: ...22650 County Highway 6 PO Box 1708 Detroit Lakes MN 56502 USA 1 888 DIAL SJE 1 888 342 5753 Phone 218 847 1317 Fax 218 847 4617 w w w sjerhombus com SJE Rhombus 08 17 1036912f ...

Page 31: ...ñado específicamente para Sistemas de Bombeo de Presión Constante El controlador VFDC 4100 es capaz de mantener una presión de descarga constante mediante el ajuste de la velocidad de hasta 4 variadores de frecuencia VFDs un VFD y hasta 3 a través de la línea de arrancadores ATL o una bomba Jockey y hasta 3 bombas principales ...

Page 32: ...stalar o efectuar mantenimiento de este producto La instalación y mantenimiento debe ser efectuada por personal idóneo siguiendo los diagramas de instalación y códigos eléctricos EXPLOSIÓN O INCENDIO NO utilice este producto con líquidos inflamables NO lo instale en lugares peligrosos como los definidos en el Código Eléctrico Nacional ANSI NFPA 70 NO instale en áreas con polvo excesivo o conductiv...

Page 33: ...s menús de configuración 10 3 3 Configuración de pantalla y métodos de entrada 14 Capítulo 4 4 1 Esquema del circuito Triplex VFD VFD 16 4 2 Esquema del circuito de controlador Triplex VFD 17 4 3 Esquema del circuito Triplex VFD 1VFD ATL 18 4 4 Esquema del circuito de controlador Triplex 1VFD ATL 19 Capítulo 5 5 1 Solución de problemas 20 Capítulo 6 6 1 Falla de alarma y acciones correctivas 21 6 ...

Page 34: ...Controlador Vista Frontal Vista posterior Pantalla LCD Indicadores LED Botones de funcionamiento CN2 Sensor Terminal Puerto CN10 COMM CN7 Entradas de Falla CN8 Baja Succión Presión Establecida 2 CN1 Velocidad Análoga Refs CN3 Salidas del Transistor CN5 Salidas de Relé CN4 Entrada de Poder DC ...

Page 35: ...FDC 4100 Manual del Usuario 3 1 2 Dimensiones del Controlador en Pulgadas Dimensiones del Controlador en Pulgadas Dimensiones del Controlador en Pulgadas Utilizar el controlador para alinear con los 8 orificios de los tornillos ...

Page 36: ...á la alternancia cuando el tiempo total de funcionamiento de la bomba principal alcanza el tiempo de alternancia programado el sistema selecciona automáticamente la próxima bomba en la secuencia para ser la principal Esta función está diseñada para permitir un mejor ciclo de vida del sistema El sistema hace que todas las bombas funcionen por igual período de tiempo para evitar que el exceso de uso...

Page 37: ...la vida útil del monitor LCD Esta función se puede desactivar si se desea Función de la bomba Jockey El rol de la bomba Jockey es mantener la presión constante durante condiciones de bajo flujo Cuando se utiliza la bomba jockey es típicamente más pequeña que las bombas principales y es muy adecuada para manejar las variaciones de bajo flujo Cuando la demanda de flujo excede la capacidad de la bomb...

Page 38: ... VALOR D 1 0 200 PID CYC TIEMPO 120 Msec 50 999 Msec ALTERNACION 24 HORAS 0 999 HORAS FRICCION 0 0 PSI 0 650 PSI CONTROL RETRASO DE MARCHA 1 SEGUNDO 0 10 SEGUNDOS SEC RETRASO DE PARADA 1 SEGUNDO 0 999 SEGUNDOS SEC RET PARADA DE JOCKEY 5 SEGUNDOS 0 999 SEGUNDOS SEC TIPO DE OPERACION VFD VFD 1VFD ATL RETRA SUCSION BAJA 30 SEGUNDOS 10 999 SEGUNDOS SEC REAJUSTAR SUC BAJA AUTO AUTO MANUAL RET REAJ SUC ...

Page 39: ...O SISTEMA SALIDA 3 ALARMA GENERAL ALARMAGENERAL BAJA SUCCIÓN BOCINA TIMBRE SALIDA 4 NO USADO P1 P4VFD FUNCIONANDO P1 P4 ALT FUNCIONANDO SALIDA 5 NO USADO BAJA PRESIÓN ALTA PRESIÓN SALIDAS DIGITALES 6 13 NO USADO VFD1 4 FLT HOA FALLA DEL SENSOR LANGUAJE ENGLISH ENGLISH ESPANOL UNIDAD DE PRESION PSI PSI BAR ADJUSTE DE PROGRAMA NO USADO NOSEUSA A TIEMPO SEMANAL MENSUAL PROGRAMAR 00 00 00 00 00 00 NO ...

Page 40: ... pedirá una contraseña si la función está habilitada Utilizando los botones de flecha vaya a la opción deseada y pulse ENTER Navegue con los botones de flecha y escoja una opción para mostrar su valor Pulse ENTER para cambiar el valor utilizando las teclas de flecha y pulse de nuevamente el botón ENTER para aceptar el nuevo valor o presione ESC para salir sin guardar Pulse la tecla ESC ENTER y bot...

Page 41: ...entrada CN7 STOP se visualiza si ninguno de los interruptores HOA están en posición AUTO 4 Frecuencia de salida VFD Indica el valor de salida del VFD funcionando La salida del VFD se puede configurar en porcentaje o en frecuencia 50 Hz o 60 Hz 5 Estado de la Bomba Inactivo Funcionando Fallo del VFD o Jockey 6 Número de bomba Visualización del total de las bombas y de la principal La bomba principa...

Page 42: ...esactivada por defecto INPUT PASSWORD 0 0 0 0 04 12 01 Ver 1 03 3 2 Detalles de los menús de configuración 3 2 1 Configuración de Fecha Tiempo Configuración de la hora actual Menús Configuración de Menú Contenidos Rango de Entrada ANOS Muestra Ano Actual 0000 9999 MES Muestra Mes Actual 1 12 FECHA Muestra Fecha Actual 1 31 FECHA FIA Muestra Dia Actual Lunes Domingo HORA Muestra Hora Actual 0 23 MI...

Page 43: ...iar RETRA BAJA PRESION Tiempo de retraso antes de parar el bombeo 10 999 SEC debido a falla de baja presión INICIAR Todos los parámetros ajustados a los valores predeterminados Si No de fábrica Excepto Datos de Configuración Menús Configuración de Menú Contenidos Rango de Entrada PRESION ESTABLECER PRESION Presión establecida para el sistema 2 PSI 650 PSI ESTABLECER PRESION 2 Para cambiar la presi...

Page 44: ...nará Si alcanza 5 600 Segundos la presión establecida durante este tiempo el sistema cambiará a PID de inmediato 3 2 7 Configuración de Proteccion Menús Configuración de Menú Contenidos Rango de Entrada PREVENCION REPOSO Cuando se establece en USADA si la bomba USADO NO USADO principal no ha sido utilizada en 10 días el sistema encenderá la bomba principal automáticamente a la velocidad mínima de ...

Page 45: ...ADAS OFF BOMBEANDO ALARMA GENERAL BAJA SUCCIÓN BOCINA TIMBRE P1 P4 VFD FUNCIONANDO P1 P4 ALT FUNCIONANDO BAJAPRESIÓN ALTAPRESIÓN VFD1 4FLT HOA FALLADELSENSOR LENGUAJE Selección de Lenguaje English Espanol UNIDAD DE PRESIÓN Unidad de medida para la entrada análoga PSI BAR 3 2 9 Configuración de Comunicación RS 485 Menús Configuración de Menú Contenidos Range de Entrada PARITY Seleccione el tipo de ...

Page 46: ...as seleccionar Fecha Hora en el menú de configu ración Figura 1 2 Moverse a la posición que necesita modificar año mes día semana apretando las teclas derecha e izquierda Presione la tecla ENTER y edite cuando parpadea 3 Cambie valores utilizando las teclas de arriba abajo 4 Guardar el valor modificado pulsando la tecla ENTER 5 Salir a la pantalla principal pulsando la tecla ESC DATE TIME PUMP SET...

Page 47: ...SOR VFD PROTECT SYSTEM PROGRAM COMM SET ALARMS DATA LOG PRESSURE SETUP 60 0 RUN SET PRESSURE 60 PSI HIGH PRE LIMIT 150 PSI LOW PRE LIMIT 20 PSI Pulse el botón MENU Utilice las teclas ARRIBA ABAJO y DERECHA IZQUIERDA para ir al Menú de Presión Pulse la tecla Enter para abrir el Menú de Presión Moverse a la posición que necesita modificar utilizando las teclas ARRIBA ABAJO Pulse la tecla ENTER Utili...

Page 48: ...0 Manual del Usuariol Capítulo 4 4 1 Esquema de Circuito Eléctrico Típico para un Sistema Triplex VFD OPER TYPE VFD OPCIONAL CON INTERRUPTOR PRINCIPAL Y PUERTA DE GABINETE CON LLAVE 480VAC ALIMENTACIÓN DE ENTRADA BOMBA 1 BOMBA 2 BOMBA 3 ...

Page 49: ...SJE Rhombus Controlador VFDC 4100 Manual del Usuario 17 RS 485 CN10 4 2 Esquema de Circuito Típico para un Controlador Triplex OPER TYPE VFD ...

Page 50: ...plex VFD OPER TYPE 1VFD ALT 18 SJE Rhombus Controlador VFDC 4100 Manual del Usuario BOMBA 1 BOMBA 2 BOMBA 3 ALIMENTACIÓN DE ENTRADA OPCIONAL CON INTERRUPTOR PRINCIPAL Y PUERTA DE GABINETE CON LLAVE NOTA TODAS LAS BOMBAS DEBEN SER DEL MISMO TAMAÑO DE 15HP O MENOS ...

Page 51: ...SJE Rhombus Controlador VFDC 4100 Manual del Usuario 19 4 4 Esquema de Circuito Típico para un Controlador Triplex OPER TYPE 1VFD ATL RS 485 CN10 ...

Page 52: ...sario Revizar que la válvula de reflujo Consulte con su mecánico contratista Presión anormal en el tanque de presión Consulte con su mecánico contratista Insuficiente capacidad en el tanque de presión Consulte con su mecánico contratista Voltaje anormal Revizar el voltaje Motor defectuoso Consulte con su mecánico contratista Bomba dañada Consulte con su mecánico contratista Filtración de objetos e...

Page 53: ...a funcionando Reiniciar Si REAJUSTAR SUC BAJA LOW SUCTION RST está en MANUAL presione el botón de REINICIO RESET para limpiar la alarma Salida La pantalla LCD muestra la luz LED de ERROR y la bocina suena Acciones Revize la presión de succión cañería el cableado de bajo nivel de agua y cambie el sensor de bajo nivel de agua El sistema parara si la alarma por más tiempo que el establecido referirse...

Page 54: ... Data Log Presione ENTER para visualizar Pantalla de Configuración de Menú Use las flechas o para elegir entre OPERA DATA RUN TIME 6 2 Pantalla de datos de alarma Alarma de la pantalla de vista de datos Método de Reconocimiento El sistema es capaz de registrar un total de 32 datos Registra y muestra la alarma secuencialmente por número fecha tiempos que ocurren y tipo de alarma Flechas ARRIBA ABAJ...

Page 55: ...1P 0 I1E VFD 1 Error 12 23 14 43 33 0 0 1P 0 I2E VFD 2 Error 12 23 14 43 33 0 0 1P 0 I3E VFD 3 Error 12 23 14 43 33 0 0 1P 0 I4E VFD 4 Error 12 23 14 43 33 0 0 1P 0 LPS Parada de Baja Presión 12 23 14 43 33 0 0 1P 0 Sop Sensor Abierto 12 23 14 43 33 0 0 1P 0 Sap Falta de Sensor 12 23 14 43 33 0 0 1P 0 LWS Grabación de bajo nivel de agua de detiene cuando se suministra alimentación Se Muestra como ...

Page 56: ...re R 002 low pressure R 004 VFD1 fault HOA R 008 VFD2 fault HOA R 016 VFD3 fault HOA R 032 VFD4 fault HOA R 064 low water alarm R 128 low pressure alarm R 256 sensor open R 512 sensor short R 1024 low water stop Time setup 1 year R 8001 32 769 2xxxx 2 month R 8002 32 770 xx 3 day R 8003 32 771 xx 4 week R 8004 32 772 xx 5 hour R 8005 32 773 xx 6 min R 8006 32 774 xx 7 sec R 8007 32 775 xx Pump set...

Page 57: ...r adjust R 8402 33 794 sensor adjust VFD setup 1 VFD stop time R 8501 34 049 sec 2 VFD minimum rate R 8502 34 050 3 VFD stop rate R 8503 34 051 4 VFD display type R 8504 34 052 5 VFD auto rest R 8505 34 053 no Protection setup 1 freeze prevention R 8601 34 305 0 not used 1 used 2 fix prevention R 8602 34 306 0 not used 1 used 3 password use R 8603 34 307 0 not used 1 used 4 password R 8604 34 308 0...

Page 58: ...plícita por lo que la limitación anterior puede a que no se aplique en su caso Algunos estados no permiten la exclusión o limitación de daños incidentales o consecuentes por lo que la limitación o exclusión anterior puede a que no se aplique en su caso Esta garantía le da usted derechos legales específicos y usted también puede tener otros derechos que varían de estado a estado PARA OBTENER EL SER...

Page 59: ..._______________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ ________________________________________________________________________________________ _____________________________________________________________________________...