SJE-Rhombus VFDC-4100 Controller User Manual
23
6.3.1 Operation Data Log Screen
It is able to record total 2000 data. Records and displays in the following format: Month/Date, Hour: Minute: Second,
Current Pressure, Lead Pump, Current Output and Condition.
UP/DOWN KEY: Scroll the list each 1 line. RIGHT/LEFT KEY: Scroll the list each 60 lines.
6.3.2 Records List
Records regularly while operating. Set the system when the system is operating.
Records regularly based on the Operation Data Interval set value.
“12/23
14:43:33 0.0
1P
0%”
Records when an alarm occurred.
“12/26 14:43:33
0.0
1P
0%Hip”
High Pressure Alarm
“12/23 14:43:33
0.0
1P
0%LoP”
Low Pressure Alarm
“12/23 14:43:33
0.0
1P
0%LoW”
Low Water Alarm
“12/23 14:43:33
0.0
1P
0%I1E”
VFD 1 Error
“12/23
14:43:33 0.0
1P
0%I2E”
VFD
2
Error
“12/23
14:43:33 0.0
1P
0%I3E”
VFD
3
Error
“12/23
14:43:33 0.0
1P
0%I4E”
VFD
4
Error
“12/23 14:43:33
0.0
1P
0%LPS”
Low Pressure Stop
“12/23
14:43:33 0.0
1P
0%Sop”
Sensor
Open
“12/23
14:43:33 0.0
1P
0%Sap”
Sensor
Shortage
“12/23 14:43:33
0.0
1P
0%LWS”
Low Water Stop Records when power is supplied.
Displays as “12/23
14:43:33
0.0
1P
0%Pun”
Records when the system operation starts.
Displays as “12/23
14:43:33
0.0
1P
0%RUN”
Records when the system operation stops.
Displays as “12/23
14:43:33
0.0
1P
0%STP”
1. RUN TIMES
A record of each pump run time is logged on this screen.
OPERA DATA
(0.0/RUN)
P1:
10 HOURS
42 MINS
P2:
10 HOURS
47 MINS
P3:
2 HOURS
41 MINS
P4:
0 HOURS
0 MINS
OPERA DATA
(0.0/RUN)
12/24 13:24:08 4.0 1P 78%
12/24 13:29:39 4.0 1P 77%
12/24 13:32:39 4.0 1P 78%
12/24 13:43:39 4.0 1P 78%
12/24 13:42:21 0.0 1P 48%LoP
12/24 13:55:21 0.0 1P 40%RUN