SJE-Rhombus VFDC-4100 Controller User Manual
13
3.2.8 System Setup
Menus
Setup Menu
Contents
Input Range
RETURN MAIN SCREEN
Returns to the main screen after set time if user
10 ~ 300
does not use any key controls
LCD BACK LIGHT TIME
After the set time, LCD back light automatically turns
10 ~ 999
off. This can be disabled by setting value to 999.
DATA LOG
Sets the sampling rate for the Operation data log
10 ~ 999
SYSTEM
TEST CODE
Internal code to check the system.
0 ~ 9999
SET UP
RELAY OUTPUT 1-5
Relay output 1-5 allows for up to 5A @ 250V
DIGITAL OUTPUT 6-13
Digital output is transistor out. High = 5V Low = 0V
Available settings for outputs are: NOT USED,
PUMPS STOPPED, PUMPING, GENERAL ALARM,
LOW SUCTION, P1-P4 VFD RUN, P1-P4 ATL RUN,
BUZZER, LOW PRESSURE, HIGH PRESSURE,
VFD 1-4 FLT/HOA, SENSOR FAULT
LANGUAGE
Language
selection
English/Espanol
PRESS UNIT
Unit of measure for analog input
PSI/BAR
3.2.9 Communication Setup (RS-485)
Menus
Setup Menu
Contents
Input Range
PARITY
Select parity mode
EVEN, ODD, NONE
COMM
BAUDRATE
Transmission speed
9600, 14400, 19200
SETUP
NODE
Network node address
1~31
DATA
BITS
8
STOP
BIT
1,2
3.2.10 Communication Setup
Menus
Setup Menu
Contents
Input Range
SCHEDULE OPERATION
This function allows the set pressure to be
NOT USED, TIMELY, WEEKLY,
00:00:00 ~ 00:00:00
adusted based on a schedle. If on certain days
MONTHLY
PROGRAM
of the week, you wanted the set pressure to be
TUESDAY
different, you would set schedule operation to
FEBRUARY
WEEKLY then set the pressures for the days of
the
week.