10
Section 6: DEBRIS SPACE
In accordance with BS 5871 part 2, minimum debris collection volumes are required
behind the installed appliance.
CLAY/CEMENT LINES OR BLOCK FLUE WHICH IS NEW, UNUSED, OR PREVIOUSLY
ONLY USED WITH A GAS FIRE.
Appliance recessed depth + 20mm
UNLINED FLUE OR CHIMNEY WHICH HAS BEEN PREVIOUSLY USED FOR A SOLID
FUEL OR OIL BURNING APPLIANCE
Appliance recessed depth + 60mm
Section 7: INSTALLATION OF APPLIANCE
Always ensure that the gas supply is isolated before commencing installation of the appliance.
The fireplace opening and environment must be in compliance with specifications laid down in
the appropriate sections of these instructions.
Remove the appliance from its carton as described previously and stand on a dust sheet.
Place the coals, ceramics and fixings safely to one side.
Remove the burner from the assembly by removing the two screws at the base of the burner
tray and undoing the connecting nut to the isolation tap.
The tray is now free and may be lifted away from the base plate, lift free of the retaining clips
on each side of the burner tray.
Diagram 3
NUT
ISOLATION
TAP
SCREWS