37
Function
Code
Default
Property
Setting
Range
Name
Proportional gain 2
(Kp2)
○
○
○
◎
○
F09.13
PID adjustment
selection
0x00
Integral time 2
(Ti2)
F09.14
F09.15
0.00~100.00
0
.
00
~
10
.
00s
0.50
0.20s
0x00~0x11
LED ones
0: Keep on integral adjustment when
the frequency achieves the upper
and lower limit.
1: Stop integral adjustment when the
frequency achieves the upper and
lower limit
LED tens
0: The same with the setting direction
1: Opposite to the setting direction
F09.16
F09.17
Switchover selection
of PID parameters
0
Differential time 2
(Td2)
0.00~10.00s
0.00s
0: Without switchover
1: Switch according to the input
deviation
2: Switch according to terminal.
Differential time 1
(Td 1)
○
○
Integral time1
(Ti 1)
F09.05
F09.06
0.00~10.00s
0.00~10.00s
0.20s
0.00s
○
Sampling cycle
(T)
F09.07
0.01~100.00s
0.10s
○
Output upper
limit of PID
F09.09
F09.10~100.0%
(Max.
frequency
)
100.0%
○
PID control
deviation limit
F09.08
0.0~100.0%
0.0%
○
F09.10
-100.0%~F09.09
(Max. frequency )
0.0%
Output lower
limit of PID
○
F09.11
0.0~100.0%
0.0%
Detection value
of feedback
offline
○
Detection time
of feedback
offline
F09.12
0.0~3600.0s
1.0s
Function Parameters Table