13. 2-Way Valve
2-way valve is required to control water flow while cooling operation. Role of 2-way valve is
to cut off water flow into under floor loop in cooling mode when fan coil unit is equipped for
cooling operation.
General Information
Type Power
Operating
Mode Supported
Closing water flow
Yes
NO 2-wire
230V 50Hz
~
AC
Opening water flow
Yes
Closing water flow
Yes
NC 2-wire
230V 50Hz
~
AC
Opening water flow
Yes
(1) : Normal Open type. When electric power is NOT supplied, the valve is open. (When
electric power is supplied, the valve is closed.)
(2) : Normal Closed type. When electric power is NOT supplied, the valve is closed. (When
electric power is supplied, the valve is open.)
How to Wire 2-Way Valve
Follow below procedures Step 1 ~ Step 2.
Step 1. Uncover front cover of the indoor unit and open the control box.
Step 2. Find terminal block and connect wire as below.
3
2
1
2 w a y v a lu e 1
2 w a y v a lu e 2
4
5
6
O F F
O N
N
O F F
O N
N
N C
N O
N
N
N C
N O
•
Normal Open type should be connected to wire (NO) and wire (N)for valve closing in cooling
mode.
• Normal Closed type should be connected to wire (NC) and wire (N)for valve closing in
cooling mode.
(NO) : Line signal (for Normal Open type) from PCB to 2-way valve
(NC) : Line signal (for Normal Closed type) from PCB to 2-way valve
(N) : Neutral signal from PCB to 2-way valve