Description: for each integrated energy meter is preset a standard description that can be changed at
any time
•
Record: by defaults all items are check for a integrated energy meter. Unchecking the item it will no
longer be stored
•
Units: change the unit of measure if necessary. By defaults all units refer to the protocol of the
integrated energy meter. Before changing this value always refer to the energy meter ModBus protocol
mapping
•
Main Filed: you can select only a single value for each configured energy meter as a primary value. The
main value will be shown in the Plant Status section, see Cap. 19
•
Register Address: report the ModBus register corresponds to the data read. Before changing this value
always refer to the energy meter ModBus protocol mapping
•
Data format: report the data format as defined in the energy meter ModBus protocol. Before changing
this value always refer to the energy meter ModBus protocol mapping
•
Multiplier: bring a multiplicative constant if necessary. This parameter is useful if in the plant are
present CT and/or TV for the energy meter
•
Offset: insert an offset if necessary
Editable fields for a non-integrated energy meter
In this case, all the parameters must be entered for the creation of readout value. This section is for technical
personnel with knowledge of the ModBus protocol.
Figura 34 - Inserting readout values
•
Description: insert a description for the readout
•
Record: enter the unit of measure for the readout
•
Main Value: check if you want associate the readout like primary value. The main value will be shown
in the Plant Status section, see Cap. 19
•
Register Address: enter the ModBus register for the readout
•
Data format: enter the ModBus data format for the readout
•
Multiplier: bring a multiplicative constant if necessary. This parameter is useful if in the plant are
present CT and/or TV for the energy meter
•
Offset: insert an offset value if necessary
NOTE: be sure to insert all the registers of interest before saving the new model. It will not be possible
to add new records after the save of the device if it is not deleting and re-inserting it.