MultiTox : DGi-TT7-E/O & DG-TT7-S
Page 29 / 60
NOSP 16452-05 (08/2016)
6.2.
Inhibition
Maintenance Inhibition is temporary. It appears during power up and maintenance.
Inhibition stops automatically when the operator gets out of the maintenance menus or after
10 minutes if communication with the TLU has been interrupted.
Maintenance inhibition can be configured in "frozen" mode (factory setting) or in "free"
mode.
•
In "frozen" mode, outputs (current and relay) remain in their previous state.
For example, if the device indicated a failure (2.0 mA), this state would be maintained
during the inhibition.
•
If the unit is configured in "free" inhibition mode, the output current will be on the
same level as for the permanent inhibition.
The permanent inhibition is activated by an order issued by the TLU when an operation is
performed at/or around the device, or when the operator wants to inhibit a faulty device. The
permanent inhibition must be removed by an operator with the TLU.In a similar way as the
maintenance inhibition, this mode will lead to a purple switch of the backlight.
6.3.
Signal current loop
State
“4-20”
[mA]
“0-22”
[mA]
Display
TLU state
Line fault
0.0
0.0
Configuration fault
2.0
2.0
DEF & yellow Backlight
DEF
Detector fault (electronic)
2.0
2.0
DEF & yellow Backlight
DEF
Measure fault
2.0
2.6
DEF & yellow Backlight
DEF
Start inhibition
2.0
3.4
INH & violet Backlight
& cycle**
Warming-up
Remaining time
including power up
Permanent inhibition
2.0
3.4
INH & violet Backlight
& cycle**
INH
Maintenance inhibition
Fixed configuration (fault) /
(“free mode ”) *
Previous
value /
(2.0)
Previous
value/
(3.4)
INH & violet Backlight
& cycle**
INH
0% of full scale
4.0
4.0
Cycle**
& green Backlight 0
No detection
No alarm
25% of full scale
8.0
8.0
Cycle**
AL1 or AL2 if reached
Alarm if level
exceeded
50% of full scale
12.0
12.0
Cycle**
AL1 or AL2 if reached
Alarm if level
exceeded
75% of full scale
16.0
16.0
Cycle**
AL1 or AL2 if reached
Alarm if level
exceeded
100% of full scale
20.0
20.0
Cycle**
& red Backlight 100 -
AL2
Alarm
105% of full scale
20.8
20.8
Alarm
(*)
Maintenance inhibition may be available in frozen or free mode.
(**) The cycle is the display sequence of the concentration, unit of measure and target gas
.
Summary of Contents for MultiTox DG-TT7-S
Page 1: ...Operating Manual NOSP 16452 05 03 2018 MultiTox Detector MultiTox DGi TT7 E DGi TT7 O DG TT7 S...
Page 2: ...MultiTox DGi TT7 E O DG TT7 S Page 2 60 NOSP 16452 05 08 2016...
Page 15: ...MultiTox DGi TT7 E O DG TT7 S Page 15 60 NOSP 16452 05 08 2016 Figure 2 Outline drawing mm...
Page 39: ...MultiTox DGi TT7 E O DG TT7 S Page 39 60 NOSP 16452 05 08 2016...
Page 54: ...MultiTox DGi TT7 E O DG TT7 S Page 54 60 NOSP 16452 05 08 2016 13 DECLARATION OF CONFORMITY...
Page 55: ...MultiTox DGi TT7 E O DG TT7 S Page 55 60 NOSP 16452 05 08 2016...
Page 56: ...MultiTox DGi TT7 E O DG TT7 S Page 57 60 NOSP 16452 05 08 2016...
Page 57: ...MultiTox DGi TT7 E O DG TT7 S Page 58 60 NOSP 16452 05 08 2016...
Page 58: ...MultiTox DGi TT7 E O DG TT7 S Page 59 60 NOSP 16452 05 08 2016...
Page 59: ......