6.8.3.
[DISP]LAY sub-menu
This menu gives access to the light intensity setting of the backlight and display:
•
AUTO : Automatic adjustment depending on the lighting environment
•
Level 0 : Backlight is switched off, minimum display
•
Levels 1 to 4 : Intermediary levels
•
Level 5 : Maximum backlight intensity
6.8.4.
[CONF]iguration
6.8.4.1.
Alarm sub-menu
The menu gives access to:
•
The number of alarms levels used (0 to 4).
•
The trigger’s value of the alarm (levels values)
•
The alarm’s trigger sense (up or down)
•
The alarm’s memorization (yes/no)
On one hand, the alarm memorization maintains relays and alarm information on the
wireless communication tool. On the other hand, the current output and the concentration
displayed on the wireless communication tool are always updated with the real
concentration
6.8.4.2.
Label and zone sub-menu
This menu allows label and zone’s modification. After selecting a label or a zone, the
modification function operates in the same manner.
The numeric keys correspond to different alphanumeric characters. For each displayed
page, the numeric keys have a different assignment.
Both “Label” and “Zone” fields are free text type for identification of the detector (name and
position of the detector).
To edit fields select [label] or [zone].
•
Press on the corresponding numeric key to select a figure
•
Press [>>] to go to the next figure in the field
•
Press [PAGE] to go next page
The label or zone modification must be confirmed by pressing the key VALID, otherwise the
modification is not taken into account
6.8.4.3.
Output configuration sub-menu
[Adjust] / [Config] / [Outputs]
This menu gives access to the configuration of the relay operating mode and to conditions of
activations.
State of the relays:
Each relay can be configured:
•
Normally open (not energized)
•
Normally closed (energized)
Summary of Contents for MultiTox DG-TT7-S
Page 1: ...Operating Manual NOSP 16452 05 03 2018 MultiTox Detector MultiTox DGi TT7 E DGi TT7 O DG TT7 S...
Page 2: ...MultiTox DGi TT7 E O DG TT7 S Page 2 60 NOSP 16452 05 08 2016...
Page 15: ...MultiTox DGi TT7 E O DG TT7 S Page 15 60 NOSP 16452 05 08 2016 Figure 2 Outline drawing mm...
Page 39: ...MultiTox DGi TT7 E O DG TT7 S Page 39 60 NOSP 16452 05 08 2016...
Page 54: ...MultiTox DGi TT7 E O DG TT7 S Page 54 60 NOSP 16452 05 08 2016 13 DECLARATION OF CONFORMITY...
Page 55: ...MultiTox DGi TT7 E O DG TT7 S Page 55 60 NOSP 16452 05 08 2016...
Page 56: ...MultiTox DGi TT7 E O DG TT7 S Page 57 60 NOSP 16452 05 08 2016...
Page 57: ...MultiTox DGi TT7 E O DG TT7 S Page 58 60 NOSP 16452 05 08 2016...
Page 58: ...MultiTox DGi TT7 E O DG TT7 S Page 59 60 NOSP 16452 05 08 2016...
Page 59: ......