GD1
Page 37 of 76
850-816926-EN R06
# Step description
Illustration / response
1
Clean the lenses on the TX and RX as described in
section 5.2.
2
Fill the Test Cell with CO
2
as described in the
section 4.2, but with CO
2
instead of H
2
S.
Recommended CO
2
test gas concentration is 10
000
–
100 000 ppm (1 %vol - 10 %vol).
3
Position the Test Cell in front of the receiver (RX)
as indicated in the figure.
4
Verify the response in the GD1 spectrum.
The output should change according to the length
of the Test Cell
multiplied
with the gas
concentration. Below is an example with 40000
ppm CO
2
filled into the Test Cell by breath.
Expected output value (ppm CO
2
):
𝑪
𝒄𝒆𝒍𝒍
∗ 𝟎. 𝟓𝟒 + 𝑪
𝒂𝒊𝒓
∗ 𝑷𝒂𝒕𝒉_𝒍𝒆𝒏𝒈𝒕𝒉
𝑷𝒂𝒕𝒉_𝒍𝒆𝒏𝒈𝒕𝒉
Where C
cell
and C
air
is the CO
2
concentration in respectively the
Test Cell and air.
Summary of Contents for GD1 MK3
Page 1: ...P N 850 816926 EN Rev6 Operating Manual Simtronics GD1 MK3 Toxic Open Path Gas Detector...
Page 8: ...GD1 Page 8 of 76 850 816926 EN R06 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 20: ...GD1 Page 20 of 76 850 816926 EN R06 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 42: ...GD1 Page 42 of 76 850 816926 EN R06 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 54: ...GD1 Page 54 of 76 850 816926 EN R06 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 58: ...GD1 Page 58 of 76 850 816926 EN R06 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 70: ...GD1 Page 70 of 76 850 816926 EN R06 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 72: ...GD1 Page 72 of 76 850 816926 EN R06 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 73: ...GD1 Page 73 of 76 850 816926 EN R06 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 74: ...GD1 Page 74 of 76 850 816926 EN R06 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 75: ...GD1 Page 75 of 76 850 816926 EN R06 EU DECLARATION OF CONFORMITY...