2.5.
Electrical connection and wiring
Make sure that power is disconnected or switched off before connecting any wires.
The system supplying power to the GD1 shall have a fuse allowing maximum 1 A of
current to enter the GD1.
The detector must be earthed for electrical safety and to limit the effects of radio
frequency interference. Earth connection points are provided on the underside of the
GD1 housing and inside the Junction Box.
The connection terminals are accessed by removing the covers of the junction boxes.
Wiring diagrams are shown below. The system cable only goes to the transmitter unit. The
cable between the junction boxes carries the power to the receiver and the
communication signals. Unless otherwise instructed, please observe that the system power
and analogue output cable is terminated on the transmitter side of the GD1 system.
Summary of Contents for GD1 MK3
Page 1: ...P N 850 816926 EN Rev6 Operating Manual Simtronics GD1 MK3 Toxic Open Path Gas Detector...
Page 8: ...GD1 Page 8 of 76 850 816926 EN R06 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 20: ...GD1 Page 20 of 76 850 816926 EN R06 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 42: ...GD1 Page 42 of 76 850 816926 EN R06 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 54: ...GD1 Page 54 of 76 850 816926 EN R06 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 58: ...GD1 Page 58 of 76 850 816926 EN R06 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 70: ...GD1 Page 70 of 76 850 816926 EN R06 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 72: ...GD1 Page 72 of 76 850 816926 EN R06 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 73: ...GD1 Page 73 of 76 850 816926 EN R06 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 74: ...GD1 Page 74 of 76 850 816926 EN R06 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 75: ...GD1 Page 75 of 76 850 816926 EN R06 EU DECLARATION OF CONFORMITY...