GD1
Page 30 of 76
850-816926-EN R06
3.3.2.
Using a HART® for tuning of signal strength
For tuning of signal strength and setting of transmission reference level, use the Alignment
Interface Unit and a HART® terminal.
#
Step description
Illustration / response
1
Clean the lenses of both transmitter (TX) and
receiver (RX) for any dirt before proceeding.
The optical path should be clear at the time
of aligning (avoid fog, mist, steam, rain,
snow, etc.).
2
Connect the HART® terminal between
terminal 7 and 2, in parallel with a resistor as
shown in the figure to the right.
See section 0 for a more detailed description
on HART®.
3
On the HART® terminal start the “Alignment
procedure”. This can be found in the
following path:
Configuration
Setup
Alignment
4
On the HART® terminal enter the command:
#SM
Terminal response:
SM
Analogue loop 1 (terminal 7) and
loop 2 (terminal 8) will output
2 mA.
The system is now entering Service Mode. Using HART®, it is necessary to go through
Service Mode to enter or exit Alignment Mode.
Summary of Contents for GD1 MK3
Page 1: ...P N 850 816926 EN Rev6 Operating Manual Simtronics GD1 MK3 Toxic Open Path Gas Detector...
Page 8: ...GD1 Page 8 of 76 850 816926 EN R06 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 20: ...GD1 Page 20 of 76 850 816926 EN R06 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 42: ...GD1 Page 42 of 76 850 816926 EN R06 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 54: ...GD1 Page 54 of 76 850 816926 EN R06 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 58: ...GD1 Page 58 of 76 850 816926 EN R06 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 70: ...GD1 Page 70 of 76 850 816926 EN R06 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 72: ...GD1 Page 72 of 76 850 816926 EN R06 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 73: ...GD1 Page 73 of 76 850 816926 EN R06 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 74: ...GD1 Page 74 of 76 850 816926 EN R06 THIS PAGE LEFT INTENTIONALLY BLANK...
Page 75: ...GD1 Page 75 of 76 850 816926 EN R06 EU DECLARATION OF CONFORMITY...