6-5
The Edit SMPL function has the following parameters:
•
Max. number of Equations: 40
•
Max. number of Statements (Input or Output combined) per Equation: 6
01:
Input Side
ALARM 18-01
OR DETECT 18-04
End of Input
HOLD ON 20-01 PRI 9,9
End of Output
02:
Input Side
ON
28-01
End of Input
HOLD OFF 20-01 PRI 9,9
End of Output
Tables 6-2 through 6-4 show valid operator codes that are supported from front
panel programming.
Table 6-2. SMPL Input Qualifiers Table
OPCODE (Qualifier)
DESCRIPTION
FIRE DET
Fire Detect State
FIRE Fire
State
FIRE ACK
Fire Acknowledge State
SUPV Supervisory
State
SUPV ACK
Supervisory Acknowledge State
TBL Trouble
State
TBL ACK
Trouble Acknowledge State
ON/CODE Oncoding
State
COMP CNST
Compare to a constant value
OFF Off
State
ANY
Any Number of elements in a List
ALL
All element in a List
DELAY CNST
Delay for a constant value
Table 6-3. SMPL Input Operators Table
OPCODE MNEMONIC DESCRIPTION
29 NOT NOT
operator
31 AND AND
operator
30
OR
OR operator
Continued on next page
SMPL Programming
Edit SMPL
Sample Program
Valid Operator Codes and
Parameter Tables
(where 18 is the card address number
and 01/ 04 is the point number)
(where 9,9 indicates the point’s set
and reset priorities respectively)
Technical Manuals Online! - http://www.tech-man.com
Summary of Contents for LifeAlarm 4005 Series
Page 2: ...this is blank text Technical Manuals Online http www tech man com ...
Page 6: ...this is blank text Technical Manuals Online http www tech man com ...
Page 58: ...this is blank text Technical Manuals Online http www tech man com ...
Page 80: ...this is blank text Technical Manuals Online http www tech man com ...
Page 141: ...Technical Manuals Online http www tech man com ...
Page 142: ...This Page intentionally left blank Technical Manuals Online http www tech man com ...