3-15
When using the input condition qualifier TBL ACK (Trouble Acknowledge), a
statement is true when the point indicated in Field 4 is in trouble. Field 4
choices for the TBL ACK qualifier are:
]
•
CPU Card Points
•
System Card Points
•
Power Supply Points
•
Digital Pseudo Points
Note:
The statement holds true until the point indicated in Field 4 (in
trouble) is Acknowledged.
Field 1
Field 2
Field 3
Field 4
[
]
[
]
[
7%/$&.
]
[
]
Figure 3-24. An Example That Contains the Condition TBL ACK
Example: The condition of 03-01 is TBL ACK. The input of the equation
remains true until the point indicated in Field 4 is acknowledged
from the FACP.
When using the input condition qualifier ON/CODE (On Coding), a statement is
true when the point indicated in Field 4 is On or Coding. Field 4 choices for the
ON/CODE qualifier are:
•
CPU Card Points
•
System Card Points
•
Power Supply Points
•
Digital Pseudo Points
•
Analog Pseudo Points
Note:
The statement holds true until the point indicated in Field 4 is OFF.
Field 1
Field 2
Field 3
Field 4
[
]
[
]
[
21&2'(
]
[
]
Figure 3-25. An Example That Contains the Condition Qualifier
ON/CODE
Example: The condition of 03-01 is ON/CODE. The input of the equation
remains true until the point indicated in Field 4 is OFF.
Continued on next page
Input Field 3 and Input Field 4,
Continued
Using the TBL ACK Qualifier
Using the ON/CODE and OFF
Qualifiers
FIRST STATEMENT
FIRST STATEMENT
Technical Manuals Online! - http://www.tech-man.com
Summary of Contents for LifeAlarm 4005 Series
Page 2: ...this is blank text Technical Manuals Online http www tech man com ...
Page 6: ...this is blank text Technical Manuals Online http www tech man com ...
Page 58: ...this is blank text Technical Manuals Online http www tech man com ...
Page 80: ...this is blank text Technical Manuals Online http www tech man com ...
Page 141: ...Technical Manuals Online http www tech man com ...
Page 142: ...This Page intentionally left blank Technical Manuals Online http www tech man com ...