5-22
Pt. TYPE:
RVISUAL
Description:
Visual (on until reset)
Operates on General Alarm
Circuit Status
LCD Readout (2
nd
line)
LED
On Visual
ON
Off Visual
OFF
Visual
CODING
Disabled TBL
Visual
TROUBLE
T
Off Auto TBL
Visual
TROUBLE
T
Detailed Description:
Used on visual alarm device circuits that must be ON
until the system reset key is pressed (not supervised).
Figure 5-58. RVISUAL Point Type
Pt. TYPE:
CODED
Description:
Coded Relay (PNIS)(normally off)
Operates on General Alarm
Circuit Status
LCD Readout (2
nd
line)
LED
On Coded
Relay
ON
Off Coded
Relay
OFF
Coded
Relay
CODING
Disabled TBL
Coded Relay
TROUBLE
T
Off Auto TBL
Coded Relay
TROUBLE
T
Detailed Description:
Relay will track any PNIS code zone.
NOTE:
PNIS is not available with the 4005 at this time.
Figure 5-59. CODED Point Type
Pt. TYPE:
SWATER
Description:
Waterflow Relay (on until silence)
Operates on General Alarm
Circuit Status
LCD Readout (2
nd
line)
LED
On WaterFlow
Relay
ON
Off WaterFlow
Relay
OFF
WaterFlow
Relay CODING
Disabled TBL
WaterFlow Relay
TROUBLE
T
Off Auto TBL
WaterFlow Relay
TROUBLE
T
Detailed Description:
Used in applications where a waterflow signal circuit is
required which will remain activated until the silence key is pressed. Activated
from a zone with the point type WATER.
Figure 5-60. SWATER Point Type
Continued on next page
Point Type Messages for Auxiliary Relay Points,
Continued
Auxiliary Relay Points
(continued)
Technical Manuals Online! - http://www.tech-man.com
Summary of Contents for LifeAlarm 4005 Series
Page 2: ...this is blank text Technical Manuals Online http www tech man com ...
Page 6: ...this is blank text Technical Manuals Online http www tech man com ...
Page 58: ...this is blank text Technical Manuals Online http www tech man com ...
Page 80: ...this is blank text Technical Manuals Online http www tech man com ...
Page 141: ...Technical Manuals Online http www tech man com ...
Page 142: ...This Page intentionally left blank Technical Manuals Online http www tech man com ...