5-24
Pt. TYPE:
PRIMARY
Description:
Elevator Capture (primary)
Operates on General Alarm
Circuit Status
LCD Readout (2
nd
line)
LED
On
Pri Elevator Relay
ON
Off
Pri Elevator Relay
OFF
Pri Elevator Relay
CODING
Disabled TBL
Pri Elevator Relay
TROUBLE
T
Off Auto TBL
Pri Elevator Relay
TROUBLE
T
Detailed Description:
Used for any relay connected to the elevator controls to
provide primary floor elevator capture. By default, these relays pick on any
alarm.
Figure 5-64. PRIMARY Point Type
Pt. TYPE:
ALTERN
Description:
Elevator Capture (alternate)
Circuit Status
LCD Readout (2
nd
line)
LED
On
Alt Elevator Relay
ON
Off
Alt Elevator Relay
OFF
Alt Elevator Relay
CODING
Disabled TBL
Alt Elevator Relay
TROUBLE
T
Off Auto TBL
Alt Elevator Relay
TROUBLE
T
Detailed Description:
Used for any relay connected to the elevator controls to
provide alternate floor elevator capture.
Figure 5-65. ALTERN Point Type
Pt. TYPE:
AHUR
Description:
AHU On / Off (single relay control)
Operates on General Alarm
Circuit Status
LCD Readout (2
nd
line)
LED
On AHU
Relay
ON
Off AHU
Relay
OFF
AHU
Relay
CODING
Disabled TBL
AHU Relay
TROUBLE
T
Off Auto TBL
AHU Relay
TROUBLE
T
Detailed Description:
Used where one auxiliary relay performs AHU ON and
OFF control.
Figure 5-66. AHUR Point Type
Continued on next page
Point Type Messages for Auxiliary Relay Points,
Continued
Auxiliary Relay Points
(continued)
Technical Manuals Online! - http://www.tech-man.com
Summary of Contents for LifeAlarm 4005 Series
Page 2: ...this is blank text Technical Manuals Online http www tech man com ...
Page 6: ...this is blank text Technical Manuals Online http www tech man com ...
Page 58: ...this is blank text Technical Manuals Online http www tech man com ...
Page 80: ...this is blank text Technical Manuals Online http www tech man com ...
Page 141: ...Technical Manuals Online http www tech man com ...
Page 142: ...This Page intentionally left blank Technical Manuals Online http www tech man com ...