3-21
Field 3 contains the Set and Reset Priorities of control equipment (relays). This
eliminates confusion of when a point is under control of one statement and
another statement tries to take control (see Figure 3-32).
Field 1
Field 2
Field 3
[
+ROG2Q
]
[
]
[
]
Figure 3-32. Field 3 Showing the Set and Reset Priorities
In Figure 3-32, point 20-02 will HOLD ON (IF the Input is true) at a Set priority
of 9. This Output statement maintains control of this point until another output
statement with an equal (9) or greater Set priority takes over. The possible
ranges for a priority are from 1 to 15, 1 being the highest and 15 being the lowest
priority. By default, the priority is 9. When changing a priority, press Function
and then press <
▲
> to place the cursor under the Set priority. Use <Next> and
<Previous> to scroll through the priorities. Press <
▼
> to place the cursor under
the Reset priority. Use <Next> and <Previous> to scroll through the priorities
and then press <Enter> to program the priorities selected.
Output Statements,
Continued
Output Field 3
Action
Specifier for
Field 2
Point
Set Priority
Reset
Priority
OUTPUT STATEMENT
Technical Manuals Online! - http://www.tech-man.com
Summary of Contents for LifeAlarm 4005 Series
Page 2: ...this is blank text Technical Manuals Online http www tech man com ...
Page 6: ...this is blank text Technical Manuals Online http www tech man com ...
Page 58: ...this is blank text Technical Manuals Online http www tech man com ...
Page 80: ...this is blank text Technical Manuals Online http www tech man com ...
Page 141: ...Technical Manuals Online http www tech man com ...
Page 142: ...This Page intentionally left blank Technical Manuals Online http www tech man com ...