background image

P82467-001 F 

Sheet 1 of 6

 

 

273 Branchport Ave. 
Long 

Branch, 

N.J. 

 

07740         

Thank you for using our products.

 

(800)  631-2148 
www.wheelockinc.com 

INSTALLATION INSTRUCTIONS 

MULTITONE APPLIANCES 

MT-12/24, MT4-12/24 

 

Use this product according to this instruction manual.  Please keep this instruction 

manual for future reference. 

 
 

GENERAL: 

Multitone Appliances are UL Listed for Fire Protective Service and for General Signaling Service.  They are listed for both indoor 
and outdoor use with the backboxes specified in these instructions.  (See Mounting Options A,B,C,D,E,F,G for MT models and H for 
MT4 models).  Multitone Appliances can be field set to produce any one of eight commonly used alarm tones.  Sound output can be 
field set to provide either HIGH (HI) dBA or STANDARD (STD) dBA sound output level.  Multitone Appliances can be field set for 
either 12VDC or 24VDC operation and are designed for use with either filtered or unfiltered (full-wave-rectified) input voltage.  All 
inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring by a Fire Alarm Panel. 
 

NOTE:

  All 

CAUTIONS

 and 

WARNINGS

 are identified by the symbol 

.

  All warnings are printed in bold capital letters. 

 

WARNING:  PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT.  THE 

MULTITONE APPLIANCE MUST BE FIELD SET TO THE DESIRED INPUT VOLTAGE, dBA SOUND OUTPUT 
LEVEL AND ALARM TONE BEFORE THEY ARE INSTALLED.  THIS IS DONE BY PROPERLY INSERTING A 
JUMPER PLUG AND ADJUSTING A FOUR POSITION SWITCH IN ACCORDANCE WITH THESE INSTRUCTIONS.  
INCORRECT SETTINGS WILL RESULT IN IMPROPER PERFORMANCE AND MAY DAMAGE THE PRODUCT, 
AND COULD RESULT IN PROPERTY DAMAGE, SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. 

 
 

SPECIFICATIONS:   

 

Table 1:  dBA and Current Ratings For Multitone Appliances 

 

 

 

Typical Anechoic 

Rated Reverberant dBA 

 

Input Current 

Input Current 

dBA at 10 Feet 

At 10 Feet Per UL 464 

Tone 

AMPS @ 24VDC  AMPS @ 12VDC 

At Nominal 

At Minimum 

At Nominal 

 

 

 

Input Voltage 

Input Voltage 

Input Voltage 

 

HI STD HI STD HI STD HI STD HI STD 

Horn 

0.040 

0.023 

0.100 

0.020 

101 95 88 82 91 85 

Bell 

0.014 

0.012 

0.031 

0.010 

 

 

94 89 82 75 85 79 

March 

Time 

Horn 

0.040 

0.023 

0.100 

0.020 

101 95 85 79 88 82 

Code 

Horn  0.040 

0.023 

0.100 

0.020 

101 95 85 75 85 79 

Code 3 Tone 

0.028 

0.017 

0.060 

0.015 

  97 

92 

79 

75 

82 

75 

Slow 

Whoop  0.048 

0.026 

0.100 

0.025 

101 96 88 82 88 82 

Siren 

0.036 

0.023 

0.082 

0.020 

100 95 85 82 88 82 

HI/LO 

0.020 

0.014 

0.044 

0.012 

 

 

95 90 82 79 85 79 

 
Add 25% more input current when operating the unit at maximum input voltage (15.6VDC for 12VDC models, 31VDC for 24VDC 
models). 

 

Anechoic dBA is measured on axis in a non-reflective (free field) test room using fast meter response.   For peak dBA (measured with 
peak meter response), add 5 dBA to typical anechoic values shown in Table 1.  Reverberant dBA is a minimum UL rating based on 
sound power measurements in a reverberant test room. 
 