10.4. Function monitoring
10.4.1. Supply line temperature
If the maximum permissible supply line temperature (factory setting 55 °C) is exceeded in heating mode, all valves are closed.
In cooling mode, all valves are closed if the minimum permissible supply line temperature of 15 °C is not reached.
10.4.2. Comparison of supply line / return line temperature
During heating operation, the spread between supply and return line temperature is constantly monitored. If the temperature in the return
line rises above the supply line temperature, the corresponding valve is closed.
10.5. Data export
The values set or recorded in the energy saving controller can be conveniently exported via the Flamconnect app and then used for further
logging purposes such as the commissioning log or the screed heating log.
For this purpose the exported file can be imported into the respective template.
The templates can be found at: https://simplex-armaturen.de/manuals/secos