Secos - Simplex Energy Control System
8.8. Connect the remaining cables
Supply line temperature, bus cable for activators, if necessary c/o,
if necessary ext. Condensation monitor, if necessary MODBUS,
if necessary c/o valve 0-10V).
26
Electrical connections
8.9. Connect external condensation monitor (optional accessory)
Only valid for Simplex accessories.
If other condensation monitors are used, it must be ensured that the
voltage supply of the condensation monitor is taken from the energy
saving controller and that a potential-free changeover contact is
then fed back to a 0..10V interface.
If the external condensation monitor is triggered, all valves are
closed and the pump interface is deactivated. As soon as the
condensation monitor reports no further condensation, the system
returns to regular operation.
27
External condensation monitor
12
13 11
1 2 3
Energy saving controller Condensation monitor
Secos
- Simplex Energy Control System
Installation instructions
|
Operating instructions