1. Up to 5 XSIG cards allowed per source NAC.
2. XSIG cards must be in same location as the source NACs.
3. Last XSIG card in chain requires EOLR Jumpers P3 & P4 to 

be installed in the IN position (2-3); otherwise, jumpers are installed in OUT position.

4. The source NAC is dedicated to providing a signal to the XSIG card and is wired in a Class B configuration. 
5. Minimum wire gauge is 18 AWG (0.8231 mm2).
6. Remove the 10 k, 1/2W EOL resistors from the amplifiers and XSIG Cards that accept the Constant Supervision NAC modules.

B-

B+

NAC2

SHLD

B-

B+

NAC1

Notes 2, 5

Note 1

Constant Supervision NAC card

removed to install Source NAC wiring.

Constant Supervision NACs 1&2

(if installed) are not available for use

when configured as Source NACs.

Constant Supervision NAC card

removed to install Source NAC wiring.

Constant Supervision NACs 1

(if installed) are not available for use

when configured as Source NACs.

IN1+

IN1-

IN2+

IN2-

NAC3

SHLD

B+

B-

IN1

IN2

Notes 2, 5

Note 1

NAC1

B+

B-

SHLD

IN1+

IN1-

P3

OUT IN

EOLR

P4

OUT IN

IN1

IN2

IN2+

IN2-

NAC2

NAC3

Note 3

P3

OUT IN

EOLR

P4

OUT IN

IN1

IN2

Note 3

P3

OUT IN

EOLR

P4

OUT IN

IN1

IN2

Note 3

P3

OUT IN

EOLR

P4

OUT IN

IN1

IN2

Note 3

B+

B-

SHLD

B+

B-

B-

B+

SHLD

B-

B+

IN1+

IN1-

IN2+

IN2-

SHLD

B+

B-

B+

B-

SHLD

IN1+

IN1-

IN2+

IN2-

B+

B-

SHLD

B+

B-

IN1

IN2

NAC2

NAC1

NAC3

IN1

IN2

NAC1

NAC2

NAC3

IN1

IN2

4100-5116 Expansion Signal Card

(Constant Supervision NAC removed to install

Source NAC wiring) 

4100-5116 Expansion Signal Card

(Constant Supervision NAC removed to install

Source NAC wiring) 

4100-5116 Expansion Signal Card

(Constant Supervision NAC removed to install

Source NAC wiring) 

4100-5116 Expansion Signal Card

(Constant Supervision NAC removed to install

Source NAC wiring) 

Flex-35 / Flex-50 Amplifier
25/70 V
Analog/Digital

Source NAC

Source NAC

B+

B-

SHLD

B+

B-

B+

B-

SHLD

B+

B-

NAC1

NAC1

NAC2

Notes 4,6

Notes 4,6

 
 

Provide wiring to an amplifier (with Constant Supervision NACs) as shown in Figure 8. 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Figure 8. Wiring to an Amplifier (With Constant Supervision NACs) 

 
 
 
 

 

Continued on next page 

 
 
 
 
 

Wiring, 

Continued 

Wiring to Amplifiers 
(with Constant 
Supervision NACs)

 

firealarmresources.com

Summary of Contents for 4100-5116

Page 1: ...Card 4100 5116 This product is compatible with 4100U and 4100ES Fire Alarm Control Panels FACP IMPORTANT Verify FACP System Programmer Executive and Slave Software compatibility when installing or rep...

Page 2: ...y with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operat...

Page 3: ...for use with non alarm audio quickly and automatically switches to an audio source when a signal is detected at either input 6 Supports earth fault isolation in conjunction with the source NAC supply...

Page 4: ...N2 NAC1 IN2 NAC2 IN2 NAC3 COMM TBL NAC2 NAC3 BAUD ADDRESS MSB LSB IN1 IN2 IN2 IN2 B NAC2 B B NAC3 B LED3 LED7 LED5 LED2 LED4 LED6 LED8 Figure 1 XSIG Card Continued on next page Introduction to the Exp...

Page 5: ...ON Steadily when NAC2 is routed to Input 2 Green 7 Status of audio NAC 2 ON Steadily when NAC is ON ON Steadily when NAC detects trouble Yellow 8 NAC3 routing relay status routed to Input 2 audio use...

Page 6: ...rd to connect to any of the eight PDI connectors as shown in Figure 2 below Note Figure 2 is a general purpose illustration that applies to most 4 inch 102 mm X 5 inch 127 mm cards Figure 2 Mounting o...

Page 7: ...SW1 8 The function of these switches is as follows SW1 1 This switch sets the baud rate for the internal 4100 communications line running between the card and the 4100 CPU Set this switch to ON SW1 2...

Page 8: ...F OFF OFF 28 ON ON OFF OFF OFF ON ON 88 OFF ON OFF OFF ON ON ON 29 ON ON OFF OFF OFF ON OFF 89 OFF ON OFF OFF ON ON OFF 30 ON ON OFF OFF OFF OFF ON 90 OFF ON OFF OFF ON OFF ON 31 ON ON OFF OFF OFF OFF...

Page 9: ...luded Make sure these prerequisites are accounted for before installing the cards Conductors must test free of all grounds All wires must be between 18 AWG 0 8231 mm2 and 12 AWG 3 309 mm2 or as the lo...

Page 10: ...Card To Source NAC s NOTE 1 NOTE 1 Provide Audio NAC wiring without Constant Supervision as shown in Figure 4 Figure 4 Audio NAC Wiring without Constant Supervision Continued on next page Wiring Cont...

Page 11: ...Supervision as shown in Figure 5 Figure 5 Audio NAC Wiring with Constant Supervision Continued on next page Wiring Continued Audio NAC Wiring with Constant Supervision 1 Leave the 10 K W resistors 37...

Page 12: ...1 NOTE 1 EOLR EOLR NOTE 1 NOTE 1 4100 1266 Class B Expander option 4100 5116 Expansion Signal Card 4100 1245 Class AAdapter 4100 5116 Expansion Signal Card To Source NAC To Source NAC Provide DC NAC w...

Page 13: ...osition 4 The source NAC is wired in a Class B configuration even when the source NAC is configured as Class A 5 Minimum wire gauge is 18 AWG 0 8231 mm2 Note 4 B B NAC2 SHLD B B NAC1 Flex 35 Flex 50 A...

Page 14: ...2 Notes 2 5 Note 1 NAC1 B B SHLD IN1 IN1 P3 OUT IN EOLR P4 OUT IN IN1 IN2 IN2 IN2 NAC2 NAC3 Note 3 P3 OUT IN EOLR P4 OUT IN IN1 IN2 Note 3 P3 OUT IN EOLR P4 OUT IN IN1 IN2 Note 3 P3 OUT IN EOLR P4 OUT...

Page 15: ...igure 9 Wiring to Power Supply NACs Wiring Continued Wiring to Power Supply NACs 1 Up to 5 XSIG cards are allowed per source NAC 2 XSIG cards must be in same location as the source NAC 3 The source NA...

Page 16: ...rouble message appears when the XSIG card loses communications with the panel master Trouble message appears when the XSIG card does not match the card type configured by the Programmer Open Circuit T...

Reviews: