7
This section contains instructions on configuring the XSIG card via jumpers and DIP switches.
These jumpers are used to connect an end-of-line resistor to the inputs when the card is installed as
the last in the line of XSIG cards. The default position is OUT (Positions 1-2).
P3
Input 1: Position 2-3 (IN) when last in line of XSIG cards; otherwise, Position 1-2 (OUT).
P4
Input 2: Position 2-3 (IN) when last in line of XSIG cards; otherwise, Position 1-2 (OUT).
Switch SW1 on the XSIG card is an eight-position DIP switch. From left to right (see Figure 3
below) these switches are designated as SW1-1 through SW1-8. The function of these switches is
as follows:
SW1-1
. This switch sets the baud rate for the internal 4100 communications line running
between the card and the 4100 CPU. Set this switch to ON.
SW1-2 through SW1-8
. These switches set the card’s address within the 4100 FACP.
Refer to Table 3 for a complete list of the switch settings for all of the possible card addresses.
Note:
You must set these switches to the value assigned to the card by the
Programmer.
1
8
7
6
5
4
3
2
Figure 3. DIP Switch SW1
Continued on next page
Card Configuration
Overview
Setting the EOLR
Jumpers (P3 & P4)
Setting the Device
Address and Baud
Rate (SW1)
ON
OFF
DIP Switches SW1-2 through
SW1-8 set the Card Address.
Figure 3 shows an Address of 3.
4100 Comm. Baud Rate.
Switch (SW1-1)
Must Be Set to ON
firealarmresources.com