background image

 

 

8

 
 

Up to 250 IDNet slave devices, such as smoke detectors and pull stations, can be connected to the 
IDNet card. Class A or Class B wiring can be used to connect the IDNet card to peripherals. 

 

IMPORTANT: 

You must use the 4100-3106 IDNet card when installing Quick Connect 

devices. 

 
Class A wiring allows IDNet appliances to communicate with the IDNet card even in the event of 
an open circuit somewhere in the loop. Class A wiring requires that two wires are routed from the 
IDNet card to each IDNet appliance, and then back again to the IDNet card. 
 
Class B wiring allows “T” tapping, and therefore requires less wiring distance per installation than 
Class A. IDNet wiring does not require end-of-line resistors, because each IDNet device 
communicates directly to the IDNet card. 
 

Review these guidelines before wiring the IDNet card. 
 

 

Refer to 4100 Field Wiring Specification Document 900-242 for further information. 

 

All wiring is shielded, 18 AWG (minimum) to 12 AWG (maximum). Refer to Table 3, 
below, for specifications on each type of wire. 

Table 3. IDNet Card Wiring Lengths 

Wire Gauge 

Maximum Distance 

18 AWG 

7.14 Ohms/10,000 ft 

16 AWG 

4.59 Ohms/10,000 ft 

14 AWG 

2.82 Ohms/10,000 ft 

12 AWG 

1.77 Ohms/10,000 ft 

 

 

All wiring is supervised and power-limited. 

 

IDNet communications power is 36.25 V (maximum) at 0.5 A, 3333 BPS. 

 

All wiring that leaves the building requires overvoltage protection. Install module  
2081-9044 wherever wire enters or exits the building. A maximum of four 2081-9044 
Modules may be connected to one channel. The maximum line distance with two 
suppressors is 2500 feet. With an additional two suppressors, the maximum line distance 
is 1500 feet. 

 

For Style 4 operation:  
-  The maximum distance to any device is 10,000 feet or 40 Ohms. 
-  “T” taps are allowed. 
-  The total distance for one IDNet line is 10,000 feet. 
-  Maximum allowed line-to-line capacitance (“+” to “-” terminals) is 0.60

 

μ

F. For 

 

applications with shielded wire, be sure that the total capacitance from line to line plus 

 

the shield to either line is no more than 0.60 

μ

F. 

 

For Style 6 operation, the maximum loop distance is 2500 feet. “T” taps are not allowed. 

 

Loop wires once through the supplied ferrite bead(s) as shown in Figure 3. 

 

Continued on next page

 

Step 3.  Wiring to IDNet Peripherals 

Overview 

Guidelines 

 

Figure 4.  

The Ferrite Bead 

Summary of Contents for 4100-3101

Page 1: ...ermarket 4100 9836 IDNet Card 64 Devices Aftermarket This product is compatible with 4100U and 4100ES Fire Alarm Control Panels FACP IMPORTANT Verify FACP System Programmer Executive and Slave Softwar...

Page 2: ...to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not...

Page 3: ...following LEDs LED1 Normally off Turns on steady if the IDNet card is not communicating with the 4100 CPU LED2 Normally off Illuminates to indicate a problem with the IDNet lines Steady on indicates...

Page 4: ...laves is normally 30 VDC Output is increased to 36 VDC when it is necessary to activate large numbers of output devices on IDNet peripherals such as piezo sounders The system CPU will set the output t...

Page 5: ...onnectors Use connector P2 labeled on the back side of the IDNet card to connect to any of the eight PDI connectors as shown in Figure 2 below Figure 2 Mounting onto the Power Distribution Interface S...

Page 6: ...llows SW1 1 This switch sets the baud rate for the internal 4100 communications line running between the card and the 4100 CPU Set this switch to ON SW1 2 through SW1 8 These switches set the card s a...

Page 7: ...FF OFF OFF 28 ON ON OFF OFF OFF ON ON 88 OFF ON OFF OFF ON ON ON 29 ON ON OFF OFF OFF ON OFF 89 OFF ON OFF OFF ON ON OFF 30 ON ON OFF OFF OFF OFF ON 90 OFF ON OFF OFF ON OFF ON 31 ON ON OFF OFF OFF OF...

Page 8: ...Net Card Wiring Lengths Wire Gauge Maximum Distance 18 AWG 7 14 Ohms 10 000 ft 16 AWG 4 59 Ohms 10 000 ft 14 AWG 2 82 Ohms 10 000 ft 12 AWG 1 77 Ohms 10 000 ft All wiring is supervised and power limit...

Page 9: ...ipheral IDNet appliance Note Use ferrite beads as shown 2 Route wire from the first IDNet appliance to the next one Repeat for each appliance 3 Route wire from the last IDNet appliance to the IDNetA a...

Page 10: ...G from the IDNetA IDNetA and SHIELD outputs on TB1 of the IDNet card to a junction box Begin T tapping at the junction box The maximum wiring distance for any IDNet circuit is 10 000 feet or 0 60 F Th...

Page 11: ...IDNet card is searching for earth faults on the IDNet line When this message is displayed the IDNet card cannot show any alarms or other statuses Appears when a short is detected on the IDNet channel...

Page 12: ...574 800 Rev D...

Reviews: