This section describes the messages that may appear on the 4100 display when using the IDNet 
card. Trouble messages appear on the left as titles, and possible causes are listed to the right in the 
text. 
 

There is no output voltage from the IDNet power supply. Replace the IDNet card. 
 

Appears if one or more extra devices (i.e., devices that have not been configured for the IDNet 
channel) are found on the system, or if a device is at an incorrect address. Only one message 
appears, regardless of the number of extra devices found. Viewing the trouble log will reveal the 
extra device address. 
 

There is an open on the IDNet channel. After fixing the wiring fault, a hardware reset is required 
to reset the trouble. 
 

Appears while the IDNet card is searching for earth faults on the IDNet line. When this message is 
displayed, the IDNet card cannot show any alarms or other statuses. 
 

Appears when a short is detected on the IDNet channel. This status clears automatically when the 
short circuit is removed. 
 

Appears when devices have been configured, but none of the devices are communicating on the 
channel. This message does not appear if there are no configured devices on the IDNet channel. 
 

Appears when a device is missing. 
 

Appears when there is a faulty device or a noisy communications channel. 
 

Occurs during any of these conditions: 
 

 

24 V is not present on TrueAlarm devices. 

 

TrueAlarm sensor bases with relay driver outputs are not properly supervised. 

 

Isolator devices are in isolation mode. 

 
 

Troubleshooting 

Overview 

IDNet Power  
Monitor Trouble 

Extra Device 

Class A Trouble 

Earth Fault Search 

Short Circuit 

Channel Fail 

No Answer 

Bad Answer 

Output Abnormal 

Summary of Contents for 4100-3101

Page 1: ...ermarket 4100 9836 IDNet Card 64 Devices Aftermarket This product is compatible with 4100U and 4100ES Fire Alarm Control Panels FACP IMPORTANT Verify FACP System Programmer Executive and Slave Softwar...

Page 2: ...to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not...

Page 3: ...following LEDs LED1 Normally off Turns on steady if the IDNet card is not communicating with the 4100 CPU LED2 Normally off Illuminates to indicate a problem with the IDNet lines Steady on indicates...

Page 4: ...laves is normally 30 VDC Output is increased to 36 VDC when it is necessary to activate large numbers of output devices on IDNet peripherals such as piezo sounders The system CPU will set the output t...

Page 5: ...onnectors Use connector P2 labeled on the back side of the IDNet card to connect to any of the eight PDI connectors as shown in Figure 2 below Figure 2 Mounting onto the Power Distribution Interface S...

Page 6: ...llows SW1 1 This switch sets the baud rate for the internal 4100 communications line running between the card and the 4100 CPU Set this switch to ON SW1 2 through SW1 8 These switches set the card s a...

Page 7: ...FF OFF OFF 28 ON ON OFF OFF OFF ON ON 88 OFF ON OFF OFF ON ON ON 29 ON ON OFF OFF OFF ON OFF 89 OFF ON OFF OFF ON ON OFF 30 ON ON OFF OFF OFF OFF ON 90 OFF ON OFF OFF ON OFF ON 31 ON ON OFF OFF OFF OF...

Page 8: ...Net Card Wiring Lengths Wire Gauge Maximum Distance 18 AWG 7 14 Ohms 10 000 ft 16 AWG 4 59 Ohms 10 000 ft 14 AWG 2 82 Ohms 10 000 ft 12 AWG 1 77 Ohms 10 000 ft All wiring is supervised and power limit...

Page 9: ...ipheral IDNet appliance Note Use ferrite beads as shown 2 Route wire from the first IDNet appliance to the next one Repeat for each appliance 3 Route wire from the last IDNet appliance to the IDNetA a...

Page 10: ...G from the IDNetA IDNetA and SHIELD outputs on TB1 of the IDNet card to a junction box Begin T tapping at the junction box The maximum wiring distance for any IDNet circuit is 10 000 feet or 0 60 F Th...

Page 11: ...IDNet card is searching for earth faults on the IDNet line When this message is displayed the IDNet card cannot show any alarms or other statuses Appears when a short is detected on the IDNet channel...

Page 12: ...574 800 Rev D...

Reviews: